background image

23

www.shieldglobal.com

WARNINGS

The SHIELD Sprinklers must be installed and maintained 
in compliance with this document. Depressurize and drain 
the piping system before attempting to install, remove, 
or adjust any Sprinklers.  Failure to do so may impair the  
performance of these sprinklers. The owner is responsible 
for  maintaining  the  fire  protection  system  and  devices  in 
operation.

WRENCH DESCRIPTION

The  Sprinkler  Wrench  is  a  tool  specifically  designed  for  
installing SHIELD Sprinklers. These special wrenches must 
be used to provide the proper leverage when tightening the 
sprinkler and to minimize slippage during installation. Any 
other wrench may damage the sprinkler.

INSTALLATION

All SHIELD Sprinklers must be installed according to 

 

NFPA  13  Standards.  Deviations  from  these  requirements 
and standards or any alteration to the sprinkler itself will 
void  any  warranty  made  by  manufacturer.  In  addition,  
installation must also meet local government provisions, 
codes and standards as applicable.

The  system  piping  must  be  properly  sized  to  insure  the 
minimum required flow rate at the sprinkler. Check for the 
proper  model,  style,  orifice  size  and  temperature  rating 
prior to installation. Install sprinklers after the piping is in 
place to avoid mechanical damage, replace any damaged 
units. Wet pipe systems must be protected from freezing. 

Upon completion of the installation, the system must be 
tested per recognized standards. In the event of a thread 
task, remove the unit, apply new pipe joint compound or 
tape, and reinstall.

ADDITIONAL

Cover  Plate  -  To  install  the  conceal  cover  plate,  align  it 
with the sprinkler and slowly turn clockwise for the cover 
plates and sprinkler to lock in. Make sure the cover plate is  
securely locked in, fail to do so may cause the sprinkler to 
malfunction.

INSTALLATION SEQUENCE

Step 1. The unit must be installed in the Pendent position 
for the Concealed Sprinkler.

Step 2. Use only a non-hardening pipe joint compound or 
tape seal. Apply only to the male
threads.

Step 3. Hand tighten the sprinkler into fitting.

Step 4. For Concealed Sprinklers, use a standard wrench. 
Tighten the unit into the fitting. A lead-tight joint requires 
only  7  to  14ft.-lbs(9.5  to  19.0Nm)  of  torque.  A  tangential 
force  of  14  to  28ft.-lbs(62.3  to124.5N)  delivered  through 
a  6”(150mm)  handle  will  deliver  adequate  torque.  Once 
torque  level  reach  over  21ft.-lbs(28.6Nm)  it  may  distort 
the  orifice  seal,  resulting  in  leakage.  For  exposed  piping  
systems, the sprinkler should be oriented so the frame 
arms are parallel with the branch line pipe.

CAUTION

Do not over-tighten or under-tighten the sprinkler to 

 

compensate for inaccurate escutcheon plate adjustment.
Protection caps are used to protect its bulb and deflector. 
Please have cap on at all times during transportation and 
interior decorating.

MAINTENANCE

 
Sprinklers  must  never  be  altered  after  manufacture.  Any 
alteration such as painting and coating will directly harm 
the sprinkler and cause malfunctions. Sprinkler in contact 
with corrosive products should be replaced if they cannot 
be cleaned completely.

Visual  inspections  are  recommended  after  installation. 
After installation, a close-up inspection annually will 

 

suffice.

Inspection  and  maintenance  of  fire  protection  system  is 
the  responsibility  of  the  owner.  It  is  recommended  that  
automatic sprinkler system be inspected and tested 

 

according to local and/or national regulations.

Concealed
Sprinkler Wrench

Reviews: