www.shieldglobal.com

MODEL: SD1050, SD1055

DESCRIPTION

The  SHIELD  Sprinklers,  SD1050,  SD1055  (Glass  Bulb  Type) 
Standard and Quick Response Concealed Sprinkler, design 
incorporates state-of-the-art, heat responsive, frangible glass 
bulb design for prompt, precise operation. The die cast frame is 
more streamlined and attractive than traditional sand cast frames.

It is cast with a hex-shaped wrench boss to allow easy tightening 
from  many  angles,  reducing  assembly  effort.  This  sprinkler  is 
available  in  various  temperature  ratings    and  finishes  to  meet 
many  design  requirements.  The  recessed  pendent  should  be 
utilized  with  a  recessed  escutcheon  which  provides  up 

½

” of 

adjustments.  All  sprinklers  are  manufactured  using  the  time 
proven Belleville seal used exclusively by all major manufactures 
to ensure long life and safe operation.

SPRINKLER OPERATION

The operating mechanism is a frangible glass bulb which contains 
a heat responsive liquid. During a fire, the ambient temperature 
rises causing the liquid in the bulb to expand. When the ambient 
temperature reaches the rated temperature of the sprinkler, the 
bulb shatters.

As a result, the waterway is cleared of all sealing parts and water 
is discharged towards the deflector. The deflector is designed to 
distribute the water in a pattern that is most effective in controlling 
the fire.

MAXIMUM COVERAGE

Standard  spray  coverage  is  up  to:  Light  Hazard  =  225  square 
feet(20.9 sq.m); Ordinary Hazard = 130 square feet(12.1 sq.m) per 
NFPA 13.

TECHNICAL SPECIFICATION

RATINGS

SPRINKLER HEAD

Concealed Sprinkler

Sprinkler Identification 
Number

Standard SD1050 (bulb 
5mm),  Quick Response 
SD1055 (bulb 3mm)

Style

Concealed Sprinkler

K Factor

5.6gpm/psi

½

. (80lpm/bar

½

)

Response Time Index 
(RTI)

Standard 50
Quick Response 30

Nominal Thread Size

½

”NPT(15mm)

Orifice Size

13mm

Max. Working Pressure 175PSI(1200kPa)

Factory Hydrostatic Test  100%@500PSI(3450 kPa)

Min. Operation Pressure 7 PSI(48 kPa)

Sprinkler Temperature

Classification

Norminal Sprinkler

Temperature Rating

N.F.P.A Maximum Ambient

(Ceiling) Temp.(Allowed)

Glass Bulb Color

Ordinary

155ºF/68ºC

100ºF/38ºC

Red

Intermediate

175ºF/79ºC

150ºF/65ºC

Yellow

Intermediate

200ºF/93ºC

150ºF/65ºC

Green

Note:

 

Shield SD1055 (3-mm bulb) is FM Approved 

as standard response only. Factory Mutual do not 

approve any concealed sprinklers for quick response