CAT. No. DIM. (mm)
TOL.
D-101A
3.6 mm
±0.10 mm
D-101B
3.9 mm
±0.10 mm
D-201C
4.4 mm
±0.10 mm
D-201D
4.6 mm
±0.10 mm
D-201E
4.9 mm
±0.10 mm
D-201F
5.1 mm
±0.10 mm
D-301G
6.2 mm
±0.10 mm
D-301H
6.5 mm
±0.10 mm
D-301J
6.8 mm
±0.10 mm
D-401K
8.0 mm
±0.10 mm
D-401L
8.2 mm
±0.10 mm
D-401M
8.8 mm
±0.10 mm
D-401N
9.1 mm
±0.10 mm
1. Open the tool handles completely
to fully retract the ram.
2. Insert the stem of upper die into
the tool frame.
3. Insert the separation spring of the
lower die into the upper die
opening. Push up firmly, and
insert the lower die stem into the
hole in the ram.
NOTE:
These connectors
should not be used with
multi-conductor shielded
cables whose conductors are
solid or stranded bonded wire.
1. Remove the cable jacket
as required and prepare
the shield as shown in the
standard method
illustration.
2. When the cable inner
conductor insulation is
vinyl of .015 in, or less
thickness or Teflon* of
.010 in. or less thickness,
use foldback method 1 or
2 as ilIustrated.
3. When the shield is foil or is
spiral wrapped, use
foldback method 2.
4. When using either
foldback method, be sure
to measure the diameter
of the shield after it is
folded back. Refer to
Table 1 for proper die
selection.
*Teflon is a registered
trademark of E.I. Du Pont De
Nemours and Company
1. For a single ground wire. strip the wire 7/16 in (11mm) and
twist the strands together.
2. For two ground wires. strip each wire 1/2 in. (12mm) and twist
the two wires together.
3. If hairpinning (hooking) the ground wire is desired, strip the
wire 1/2 in . (12mm) and bend it as shown. Use one die size
larger.
1. Insert the connector, with the ground trap facing up, into the
nest area of the die. Be sure to center the connector.
2. Place the ground wire into the ground trap and the shielded
cable into the bottom to the connector. Be sure to butt the
cable jacket and the ground wire insulation against the metal
connector edge. The ground wire can exit from either direction.
3. Squeeze the tool handles completely to form the connector
around the shield.
INSTALLING THE DIES IN THE
ERG740 TOOL
1. Install the die set into the
ERG740 Tool.
2. Close the tool handles until the
die faces are touching.
3. Using calipers, measure the die
nest height and compare to the
die gauging chart to ensure die
nest opening is within the
specified tolerance range.
GAUGING THE DIES
CABLE PREPARATION
GROUND WIRE PREPARATION
INSTALLING THE CONNECTOR
ON SHIELDED CABLE
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
TA04632 B Page 2 of 2
© 2011 Thomas & Betts. All Rights Reserved.
For Parts or Service, contact the Thomas & Betts Tool Service Center at
1-800-284-TOOL (8665).
WARRANTY:
Thomas & Betts sells this product with the understanding that the user will
perform all necessary tests to determine the suitability of this product for the user's intended
application. Thomas & Betts warrants that this product will be free from defects in materials
and workmanship for the period stated on the enclosed warranty card. Upon prompt
notification of any warranted defect, Thomas & Betts will, at its option, repair or replace the
defective product or refund the purchase price. Proof of purchase is required. Misuse or
unauthorized modification of the product voids all warranties.
Limitations and Exclusions:
THE ABOVE WARRANTY IS THE SOLE WARRANTY
CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS
OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE
SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE WARRANTY IS
LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO
CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL,
INCIDENTAL OR CONSEQUENTIAL DAMAGES.
CAUTION
Do not solder dip the ground wire ends.
Do not use solid ground wire.
CAUTION
During all stripping operations, use extreme care to
prevent nicking or cutting of the shield or inner
conductor insulation. This could result in short circuits.
CAUTION
Be sure that neither the cable outer jacket nor the
ground wire insulation is under the metal portion of
the connector. This will overload the dies.
D 101 A
SHIELD
JACKET
COND. DIELECTRIC
AS
REQ.
7/16 in. (11 mm)
STANDARD METHOD
SHIELD
COND. DIELECTRIC
AS
REQ.
7/16 in. (11 mm)
JACKET
FOLDBACK METHOD 1
SHIELD ROLLED BACK
COND. DIELECTRIC
AS
REQ.
JACKET
FOLDBACK METHOD 2
2
3
4
5
UPPER DIE STEM
UPPER DIE
SEPARATION
SPRING
LOWER DIE STEM
LOWER DIE
RAM
NEST AREA
6
HAIRPIN GROUND WIRE
GROUND
WIRE
NOTE:
DO NOT FORM OR BEND
GROUND LEAD TRAP
INSULATION
1/4 in. (6 mm)
GROUND WIRE
GROUND TRAP
CABLE
Ground Wire
Dies
Dies
Cable
Connector
GROUND TRAP
D 101 A