background image

 

38 | 

P a g e

 

USER MAINTENANCE 

 

 

 

 

 

 

Summary of Contents for SMO5HP-2

Page 1: ...Installation Operation Manual SMO5HP 2 HIGH PERFORMANCE OVEN 220 240 Voltage...

Page 2: ...urge Port The SMO5HP 2 can be built with a 3 8 inch ID 9 5mm gas in port on the back of the oven This optional port can be connected to a cylinder of nitrogen N2 or other inert gas to purge the oven c...

Page 3: ...S D as forced air ovens for professional industrial or educational use where the preparation or testing of materials is done at an ambient air pressure range of 22 14 31 3 inHg 75 106 kPa and no flamm...

Page 4: ...l the Oven 17 Installation Cleaning 17 Install the Shelving 17 GRAPHIC SYMBOLS 19 CONTROL PANEL OVERVIEW 21 OPERATION 23 Operating Precautions 23 Theory of Operations 24 Put the Oven into Operation 26...

Page 5: ...s must draw up a site specific standard operating procedure SOP covering each application and associated safety guidelines This SOP must be written and available to all operators in a language they un...

Page 6: ...4897 extension 4 or 503 640 3000 FAX 503 640 1366 Sheldon Manufacturing INC P O Box 627 Cornelius OR 97113 ENGINEERING IMPROVEMENTS Sheldon Manufacturing continually improves all of its products As a...

Page 7: ...through the unit access port Select thermocouples suitable for the application temperature you will be calibrating at Why Probes Reference readings taken outside the chamber using wire temperature pr...

Page 8: ...8 P a g e INTRODUCTION...

Page 9: ...rior and exterior If you find any damage to the unit follow the carrier s procedure for claiming damage or loss 1 Carefully inspect the shipping carton for damage 2 Report any damage to the carrier se...

Page 10: ...ent Connect Wire Braid 14 gauge 6 inches 15 cm Intake Vent Exhaust Vent Control Panel Intake Vent Valve Control Exhaust Vent Valve Control Outer Door Gasket Chamber Ceiling Liner Left wall Chamber Lin...

Page 11: ...TE INFORMATION Locate the data plate on the back of the oven next to the power inlet The data plate contains the oven model number and serial number Enter this information below for future reference D...

Page 12: ...12 P a g e RECEIVING YOUR UNIT...

Page 13: ...ual Pre Installation Check that the required ambient condition for the oven are met page 14 Check that the spacing clearance requirements are met page 14 Unit dimensions may be found on page 34 Check...

Page 14: ...her channeling o Otherwise 24 inches 610mm of headspace clearance is required between the exhaust vent and any overhead cover or partition Do not place objects on top of the oven Exception A power exh...

Page 15: ...required circuit breaker is 20 Amps Oven Fuses The oven is provided with two 20 amp fuses These are located in holders adjacent to the power feed braid on the back power panel of the unit The fuses pr...

Page 16: ...fire hazard LIFTING AND HANDLING The oven is heavy Use appropriate lifting devices that are sufficiently rated for these loads Follow these guidelines when lifting the oven Lift the oven only from its...

Page 17: ...r to cleaning and installation Do not clean with deionized water See the Cleaning and Disinfecting topic in the User Maintenance section see page 31 for more information on how to clean the oven chamb...

Page 18: ...18 P a g e INSTALLATION...

Page 19: ...s adjustable temperature Indique temp rature r glable AC Power Rep re le courant alternatif I ON O OFF I indique que l interrupteur est en position marche O indique que le commutateur est en position...

Page 20: ...20 P a g e GRAPHIC SYMBOLS...

Page 21: ...ough menus and parameters lists when programming heating recipe profiles or performing a temperature calibration On the homepage it scrolls through operating parameters or profile start The gray Reset...

Page 22: ...22 P a g e CONTROL PANEL OVERVIEW...

Page 23: ...ids or fuel air mixtures in quantities that can become potentially explosive Outgassed byproducts may be hazardous to or noxious for operating personnel Exhaust should be vented to a location outside...

Page 24: ...ove the oven chamber The processor employs proportional integral derivative analytical feedback loop functions when measuring and controlling the shelving temperature PID controlled heating pulse inte...

Page 25: ...ge options when the oven is running a constant temperature set point The intended application of the power exhaust fan is to positively vent exhaust out of the workspace around the oven The standard r...

Page 26: ...Limit for your application page 27 Optional After setting the High Limit you may set the constant temperature set point to a warm up temperature or to your constant temperature baking set point Read...

Page 27: ...ultiple Times Limit High Option Push the Advance button until Lh S1 Limit High Set Point shows in the green mid level display line 2 Adjust the high limit to at least 5 C above the highest temperature...

Page 28: ...mming steps 1 Adjust the constant temperature set point on the home page Adjust Do not exceed the high limit temperature set point Note Holding down an arrow button will cause the temperature to advan...

Page 29: ...oven chamber or hardware failure turn off the oven and wait for the oven to cool to room temperature before opening chamber door Contact Technical Support for assistance Restoring Heating Perform the...

Page 30: ...mbly in place 2 Mount the power exhaust blower on the exhaust vent cover assembly a The open side of the blower mounting body should fit over the sliding damper b Align the blower and the assembly scr...

Page 31: ...eel surfaces Do not use chlorine based bleaches or abrasives these will damage the chamber liner Warning Exercise caution if cleaning the unit with alcohol or flammable cleaners Always allow the unit...

Page 32: ...ssories shelving and other non attached items from the chamber when disinfecting Disinfect all surfaces in the chamber making sure to thoroughly disinfect the corners Exercise care to avoid damaging t...

Page 33: ...d shelf sliders from the oven 2 Unscrew the nuts located at the top of the right and left chamber walls 3 Remove the chamber gasket so that there is room to pull the ceiling liner out through the door...

Page 34: ...often as required by your laboratory or production protocol or regulatory compliance schedule Always calibrate to the industry or regulatory standards required for your application A Suggested Calibr...

Page 35: ...mperature display readings a If the readings are the same or the difference between the two falls within the acceptable range of your protocol the display is accurately showing the chamber temperature...

Page 36: ...to the Temperature Calibration offset parameter a Push the green Advance button repeatedly unit i CA appears in the green mid display line and a number value in the red top line 5 Adjust the number v...

Page 37: ...the two falls within the acceptable range of your protocol the display is accurately showing the chamber temperature The calibration procedure is now complete OR b Advance to the next step if the diff...

Page 38: ...38 P a g e USER MAINTENANCE...

Page 39: ...cting the recommended wall clearances of 10 of the height width and depth of the inner chamber All indications are average values typical for units produced in the series We reserve the right to alter...

Page 40: ...5 minutes Recovery to 110 C 5 minutes after closing the door After the door has been open for 30 seconds AIRFLOW PERFORMANCE Ventilation Rates Cubic Feet per Minute 80 C Liters per Minute 80 C 7 6 215...

Page 41: ...240V 5x20mm Requires 2 fuses 3300538 Optional Power Exhaust Blower Unit 220 240 Volt 9990741 Ordering Parts and Consumables If you have the Part Number for an item you may order it directly from Shel...

Page 42: ...P O Box 627 Cornelius OR 97113 USA support sheldonmfg com sheldonmanufacturing com 1 800 322 4897 503 640 3000 FAX 503 640 1366...

Reviews: