3. The ground wire must be connected to grounding point on the unit.
Ground rod installation, select the area where moisture stored in the soil and away from fl ood area
with no sand or limestone.
The diameter of ground rod is not less than 16 millimeters and the length is not less than
240 centimeters.
Embed the ground rod at least 30 centimeters in depth from ground surface.
Grounding process.
4. Ground resistance must be less than 5 ohm.
5. After grounding process is completed, if ground resistance is higher than 5 ohm, additional ground
rod must be embedded. Leave the additional one away from the previous ground rod at least equal to
the length of ground rod. Connect them together in parallel.