13
·
16
13
Stop operation of the data link
Start operation of the data link
Writing to EEPROM or operation stop operation
Writing to EEPROM or operation start operation
Initialize parameter setting value
Instruction system
Data memory start system
Instruction system
Data memory start system
Instruction system
Data memory start system
Instruction system
Data memory start system
Address
(8)
Set contents
Setting method (value, example)
007500
Time out time of SEND/RECEIVE instruction of
master station (0.1 to 25.5 sec.)
007501
to
007577
(Octal, byte) When 10 second, set to 100
(D)
007600
PC model of master station
007601
to
007677
PC model of slave station 01 to 77
(8)
(See page 8·6 same as data link master station)
Same as 007600
00
(H)
80
(H)
00
(H)
81
(H)
00
(H)
82
(H)
00
(H)
83
(H)
007700
007701
007702
007703
007710
007711
007712
007713
007700
to
007703
System of each cannel in
SEND/RECEIVE function
Top addresses in communication
information storage area when using
data memory starting system of
SEND/RECEIVE functions
007710
to
007713
CH0
CH1
CH2
CH3
007720
007721
Number of receiving bytes of relay link in memory
capacity save function
007722
007723
Number of receiving bytes of register link in
memory capacity save function
Whether the station number information
should be output or not
007763
(Octal, word)
(Hexadecimal, byte)
007764
to
007767
007764
007765
007766
007767
Top address of flag area on each
slave station
When
コ
0600, set to 000600
(8)
(Set by file address)
00
(H)
: Do not output flag
80
(H)
: Output flag
When file number is 2, set to 02
(H)
00
(H)
01
(H)
80
(H)
81
(H)
08
(H)
007777
Do not output
Output
Set 00008
(D)
for 8 bytes
Set 00064
(D)
or 64 bytes
(Octal, byte)
(Octal, byte)
Time out time of SEND/RECEIVE instruction of
slave station 01 to 77
(8)
(See page 13·13 same as data link master station)
Top address of relay link area in
memory capacity save function
007730
to
007733
Top address of register link area in
memory capacity save function
007734
to
007737
007730
007731
007732
007733
007734
007735
007736
007737
(Octal, word)
00
(H)
00
(H)
(Octal, word)
(Hexadecimal, byte)
00
(H)
00
(H)
01
(H)
00
(H)
80
(H)
81
(H)
91
(H)
PC is ZW model or JW model, ZW-
20CM is without JW sign.
PC is ZW model, ZW-20CM is with
JW sign and JW-20CM.
PC is JW model, ZW-20CM is with
JW sign and JW-20CM/JW-22CM
This setting is valid by 80
(H)
(Octal, word)
(Hexadecimal, byte)
When
コ
1200 set to 001200
(8)
(Set by file address)
When
09000
set to 004000
(8)
(Set by file address)
When file number is 0, set to 00
(H)
007771
Communication error detection interval
32 stations max.: 250 ms, 33 stations
min.: 450 ms
Set in 100 ms unit
00
(D)
001 to 255
(D)
③
Data link slave station
※
Set in case that slave station is JW-20CM only.
(1/2)