24
Changing Operating Parameter
CAUTION
The following operation includes the changing of the trip points of voltage or frequency. Never open the front cover of the
solar power conditioner display except by an authorized installer.
• To change the trip points, follow the instructions below.
• Perform
changes
while PV module is generating power during the daytime of a sunny day. Refer to the table on page 28 of the
value. The default value is designated by bold character.
1. Stop the power conditioner manually.
Press
“POWER”
button if it is operating.
“STOP”
will be displayed on the display.
BACK
LIGHT
DISPLAY
MODE
CO
2
POWER
RESET
SOLAR POWER CONDITIONER DISPLAY
2. Remove the front cover of the display.
Refer to page 22.
3. Slide the both of two dip switches to
“SVC”
position
with a narrow tool.
The first parameter number and its value appear on the display. If the display continues to
indicate
“STOP”
, one or both switches are left
i
n INV
position
. In this
mode
, do
no
t press
“POWER”
button
!
(
“POWER”
is not indicated on the display. See below figure.),
do not make
the solar power
conditioner start operating. Confirm the both switches are
i
n
“SVC”
position
.