SHARP(CHINA)INVESTMENT CO.,LTD
6. Display EU
Problem symptom
Display EU
Cause
Voltage sensor fault
Malfunction No.
Content of diagnosis
Action
Insert again if loose.
1
The outdoor power source bord can’t check the
voltage, check the votage lower or higher than the
protector voltage .
Replace the outdoor power source board
voltage sampling circuit
7. Display EP
Problem symptom
Display EP
Cause
Temperature switch fault ( on top of the compressor)
Malfunction No.
Content of diagnosis
Action
Check the insert position CN3 of the compressor
top temperature switch wires on outdoor power
source board
Insert again if loose.
1
No switch on compressor top
Jumper short-circuiting (This function not provided for 1 – 1.5P unit)
Check the U, V and W wires of
the compressor.
The correct sequence of U. V and W wiring shall be “red, white and
blue”. Connect again if incorrect.
Check the system pressure.
The pressure is low. Add refrigerant to ensure the system pressure
is normal.
2 Compressor
temperature. The
temperature is
very high,
accompanied
with bad smell.
Check the outdoor ventilation
and if there is any obstruction
that affects the normal radiating
of the air conditioner.
Install to the position as required in the Installation Manual and
ensure the air inlet and outlet of the outdoor unit is smooth.
If the fault is solved after short circuiting, replace the shell
temperature switch.
3
Compressor temperature: The temperature is not
high. Short circuit CN3.
If the fault remains unsolved after replacing the shell temperature
switch, please replace the outdoor power source board.
8. Display P1
Problem symptom
Display P1
Cause
Overvoltage / undervoltage protection
Malfunction No.
Content of diagnosis
Action
1
Test the supply voltage if it is between 160V
̚
260V
˄
AC
˅
.
It is normal protection if exceeding this range.
2
Test if the voltage between L and N terminal of
outdoor unit is within 160V
̚
260V
˄
AC
˅
.
It is normal protection if exceeding this range.
3
If the voltage is normal:
Replace the outdoor power source board
3-14
3-14
Summary of Contents for AE-X12PSR
Page 3: ... 2 EXTERNAL DIMENSION INDOOR UNIT OUTDOOR UNIT 1 2 ...
Page 4: ... 3 WIREING DIAGRAM 1 AY X9PSR AY X12PSR AE X9PSR AE X12PSR Indoor unit Outdoor unit 1 3 ...
Page 9: ...SHARP CHINA INVESTMENT CO LTD 2 AY X9PSR AY X12PSR 2 4 ...
Page 10: ...SHARP CHINA INVESTMENT CO LTD AY X9PSR AY X12PSR 2 5 ...
Page 11: ...SHARP CHINA INVESTMENT CO LTD AY X9PSR AY X12PSR 2 6 ...
Page 12: ...SHARP CHINA INVESTMENT CO LTD 1 2 Printed wiring board Indoor unit AY X9PSR AY X12PSR 2 7 ...
Page 14: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 9 ...
Page 15: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 10 ...
Page 16: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 11 ...
Page 17: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 12 ...
Page 18: ...SHARP CHINA INVESTMENT CO LTD POWER SUPPLY BOARD AE X9PSR EX X12PSR 2 13 ...
Page 19: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR EX X12PSR 2 14 ...
Page 20: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR EX X12PSR 2 15 ...
Page 22: ...SHARP CHINA INVESTMENT CO LTD POWER SUPPLY BOARD AE X9PSR AE X12PSR 2 17 ...
Page 28: ...SHARP CHINA INVESTMENT CO LTD 2 23 ...
Page 56: ...190 40 95 40 280 795 150 SHARP CHINA INVESTMENT CO LTD 7 1 CHAPTER7 INSTALLATION MANUL ...
Page 57: ...70 80 10 SHARP CHINA INVESTMENT CO LTD 7 2 ...
Page 58: ...SHARP CHINA INVESTMENT CO LTD 7 3 ...
Page 59: ...70 80 10 1 SHARP CHINA INVESTMENT CO LTD 7 4 ...
Page 60: ...SHARP CHINA INVESTMENT CO LTD 6 1 CHAPTER 6 OPERATION MANUAL ...
Page 61: ...SHARP CHINA INVESTMENT CO LTD 6 2 ...
Page 62: ...50 13 3 50 SHARP CHINA INVESTMEN T CO LTD 6 3 ...
Page 63: ...SHARP CHINA INVESTMENT CO L TD 6 4 ...
Page 64: ...24 18 46 21 27 7 SHARP CHINA INVESTMENT CO LTD 6 5 ...