9. Display E9 (Firstly display P0 or P9, then change to E9)
Problem symptom
Display E9 (Firstly display P0 or P9, then change to E9)
Cause
Intelligent power module of drive and module fault
Malfunction No.
Content of diagnosis
Action
If this code is displayed when the compressor is
started for several seconds or even not started,
check the compressor connection for correctness
If no insert wrong, replace the intelligent power module
Check if the outdoor module is
tightly installed onto the radiating
fins and if the silicone is applied
evenly
Fix the screws again if loose.
Check the system pressure.
Recharge refrigerant if the pressure is low. Discharge
some refrigerant if the pressure is too high.
Check the outdoor ventilation and if
there is any obstruction that affects
the normal radiating of the air
conditioner.
Install to the position as required in the Insallation
manual and ensure the air inlet and outlet of the outdoor
unit is smooth.
1
Re-energize
and check
the
protection
code on
display.
Firstly
display P0
“P0”
appears
when the
air
conditioner
is working
The above inspections are normal,
but the fault remains unsolved
Replace the intelligent power module
If this code is displayed when the compressor is
started for several seconds or even not started,
check the compressor connection for correctness
If no insert wrong, replace the intelligent power module
When the compressor is restarted immediately
after stop, this might also cause P9 protection
because the cooling system is not stable.
Try starting the air conditioner again after a longer period
of stop
Cooling / heating is normal
during run
Replace the intelligent power module
2 Re-energize
and check
the
protection
code on
display.
Firstly
display P9
P9 appears
after the air
conditioner is
started and
has run for a
period of time
If the cooling / heating is
abnormal, check the
compressor wiring for
correctness.
Insert again if loose.
10. Display EE
Problem symptom
Display EE
Cause EEPROM
fault
Malfunction No.
Content of diagnosis
Action
1
Shut off the power and suplyes again,if EE dispay again:
Replace outdoor power source board
11. Display P1
Problem symptom
Display P1
Cause
Overvoltage / undervoltage protection
Malfunction No.
Content of diagnosis
Action
1
Test the supply voltage if it is between 160V
̚
260V
˄
AC
˅
.
It is normal protection if exceeding this range.
2
Test if the voltage between L and N terminal of outdoor unit is
within 160V
̚
260V
˄
AC
˅
.
It is normal protection if exceeding this range.
3
If the voltage is normal
Replace the outdoor power source board
12. Display E0
ǃ
E5
3-15
Summary of Contents for AE-X12PSR
Page 3: ... 2 EXTERNAL DIMENSION INDOOR UNIT OUTDOOR UNIT 1 2 ...
Page 4: ... 3 WIREING DIAGRAM 1 AY X9PSR AY X12PSR AE X9PSR AE X12PSR Indoor unit Outdoor unit 1 3 ...
Page 9: ...SHARP CHINA INVESTMENT CO LTD 2 AY X9PSR AY X12PSR 2 4 ...
Page 10: ...SHARP CHINA INVESTMENT CO LTD AY X9PSR AY X12PSR 2 5 ...
Page 11: ...SHARP CHINA INVESTMENT CO LTD AY X9PSR AY X12PSR 2 6 ...
Page 12: ...SHARP CHINA INVESTMENT CO LTD 1 2 Printed wiring board Indoor unit AY X9PSR AY X12PSR 2 7 ...
Page 14: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 9 ...
Page 15: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 10 ...
Page 16: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 11 ...
Page 17: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR AE X12PSR 2 12 ...
Page 18: ...SHARP CHINA INVESTMENT CO LTD POWER SUPPLY BOARD AE X9PSR EX X12PSR 2 13 ...
Page 19: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR EX X12PSR 2 14 ...
Page 20: ...SHARP CHINA INVESTMENT CO LTD AE X9PSR EX X12PSR 2 15 ...
Page 22: ...SHARP CHINA INVESTMENT CO LTD POWER SUPPLY BOARD AE X9PSR AE X12PSR 2 17 ...
Page 28: ...SHARP CHINA INVESTMENT CO LTD 2 23 ...
Page 56: ...190 40 95 40 280 795 150 SHARP CHINA INVESTMENT CO LTD 7 1 CHAPTER7 INSTALLATION MANUL ...
Page 57: ...70 80 10 SHARP CHINA INVESTMENT CO LTD 7 2 ...
Page 58: ...SHARP CHINA INVESTMENT CO LTD 7 3 ...
Page 59: ...70 80 10 1 SHARP CHINA INVESTMENT CO LTD 7 4 ...
Page 60: ...SHARP CHINA INVESTMENT CO LTD 6 1 CHAPTER 6 OPERATION MANUAL ...
Page 61: ...SHARP CHINA INVESTMENT CO LTD 6 2 ...
Page 62: ...50 13 3 50 SHARP CHINA INVESTMEN T CO LTD 6 3 ...
Page 63: ...SHARP CHINA INVESTMENT CO L TD 6 4 ...
Page 64: ...24 18 46 21 27 7 SHARP CHINA INVESTMENT CO LTD 6 5 ...