Function

details

I. Temperature

Control

• After turning

on for the delay time ,the compressor

starts operating

when cold-room

temperature;::':

(set

temp

Hysteresis),

and will be off when cold-room

temperature

~ set temperature.

• To protect the compressor,

it can not be re-started

unless the time when the compressor

stops every time is

longer than the delay time(Parameter

E4).

2. Defrosting

Functions

• It defrosts

only if the temp.ofthe

evap.sensor

is less than the defrost termination

temp.(Parameter

F3)

• Operating

after a defrost

interval

time it will automatically

enter the status of defrost.

If the temperature

of evap. sensor is less than the defrost termination

temperature,

the defrost LED will turn on, and the

compressor

will stop.

• When the temp. of the evap. Sensor is over the temp. of defrost termination;

or the defrsot duration

ends,

the compressor

will exit the defrost status. After two minutes

dripping

time it will enter in the normal

status of refrigeration.

• When the defrost interval

time is set to "00" , the function

of automatic

defrost will be cancelled.

3. Display during defrost

• When setting the parameter

F4= l,the room temp. is locked during defrost,

and the last value before

defrost is displayed.

When defrost ends, normal display will be resumed

after 20 minutes

delay of room

temp. display. The defrost LED flashes during the delay.

4. Abnormal

work mode

• When the room sensor is short-circuited

or overheated

(more than ISO'C / lS0r)

"HH" is displayed;When

the room sensor is open-circuited

or temperature

is too low (less than -4S'C

/ -4Sr)

"LL" is displayed.

At that time the compressor

automatically

works by the cycle of 4S minutes

on and IS minutes

off.

• When the Evap. sensor fails or over the displayed

range, the defrost termination

will be just controlled

by

the defrost duration.(Parameter

F I)

S. Circuit Diagram

20A5A

/250VAC

AC

LINE

Notes

for Installation

I. The sensor cable leads must be kept separately

from main voltage wires in order to avoid high frequency

noise induced.

Separate

the power supply of the loads from the power supply of the controller.

2. When install the sensor, it shall be placed with the head upward and the wire downward;

The evaporator

sensor must be installed

between

the fins of the evaporator

in the area, where probably

the ice is the

thickest.

Don't place the evaporator

sensor near the electric

heater.

3. In case of long-distance

sensor installation

from the controller,

the sensor cable may be prolonged

up to

100 m max. without any re-calibration.

4. The temperature

controller

can not be installed

in the area with water drops.

Accessories

for the temperature

controller

I. One attached

transformer

2. Two temperature

sensors

3. One installation

stand

4. One cover panel and I <I>

3 X I Omm screw