Model: SF-I02

Digital Temperature Controller

Refrigeration LED

Defrollt LED

Features

of Function

• It is a mini-sized

and integrated

intelligent

controller

and applicable

to the compressor

of one HP.

• Main functions:

Temperature

Display/ Temperature

Control/

Manual, automatic

defrost by

turning off compressor

/ Light Control! Value Storing/ Self Testing /Parameter

Locking'

Specifications

l. Output of the outside sealed transformer:

12VAC(one transformer

matched with one temp. controller)

2. Temperature

sensor: NTC, doublc sensors (for cold-room

temp.& defrost control),2m(L)

3. Rangeoftemperaturedisplay:-45~+150'C

(-45-+150r);

Accuracy:±I'C

(±2r)

4. Range of set temperature:

-45~+45'C

(-45-+

113r);

Factory default :O'C

(32r)

5. Dimension:77(Length)

X 35(Width) X 60(Depth)mm

Mounting

hole dimension:71

(Length) X 29(Width)mm

6. Temperature

of the operating

environment:-10~60'C

(14~

140r);

Relative

Humidity:20%-90%(Non-condensing)

7. Relay output

contact capacity

• Compressor:

N.O. 20A/250VAC

(applicable

to one HP Compressor,

ifmore

it needs to connect an toAC contactor)

• Light:

N.O.

5A/250VAC

Front Panel Operation

I . Set temperature

• Press

~

button, the set temperature

is displayed.

• Press ~

or ~

button to modify and store the displayed

value. Press ~

button to exit the adjustment

and display the cold-room

temperature.

• Ifno more button is pressed within 10 seconds,

the cold-room

temperature

will be displayed.

2. Light: Press ~

button, it lights; Press again, it stops.

3. Manual start/stop

defrost: Press ~

button and hold for 6 seconds to defrost or stop defrost.

4. Display the evap. Temperature:

Press ~

button and hold for 6 seconds,

the evap. temp. is displayed,

after 10 seconds the cold-room

temp. is resumed to be displayed.

5. Refrigeration

LED: During refrigeration,

the LED is on; When the cold room temp. is constant,

the LED

is off; During the delay,

the LED flashes.

6. Defrost LED: during defrosting,

the LED is on; When it stops defrosting,

the LED is off. During the delay

display of defrost,

the LED flashes.

7. Parameter

setup

• Press ~

button for 6 seconds to enter parameter

setting, at the same time "PAS" will be displayed

and

flash;

press ~or

~

to enter a tens digit and press ~

button to confirm;and

then press ~

or ~

to enter

a single digit and press ~

button to confirm.

Ifit is correct, parameter

code EI will be displayed

(when

it is set to 00, the password

will be cancelled).

• Press again~button

to select sequentially

from the parameters:

E2,E3,E4,E5,E6,Fl

,F2,F3,F4,CI.

• Press ~

or ~

button, the value of parameter

will be displayed

and can be modified

and stored.

• Ifno more button is pressed within 10 seconds,

it will return to normal operation

mode.

Parameter

Function

Set range

Default

Parameter

Function

Set range

Default

PAS

Password

00-99

E6

Offset on evap. Temp.

-20-20

"C

0

36-36'F

EI

Lower setpoint limit

4S"C-Settemp

22'C

-4S'F

.

-8'F

FI

Max. Defrost duration

1-60Min

20Min

E2

Higb~r

setpoint limit

4S"C

10"C

F2

Defrost

interval

time

0-24Hr

4Hr

Settemp'-113'F

SO'F

F3

Defrost termination

temp.

0-4S'C

8"C

l-lO"C

S"C

32-113'F

46'F

E3

Temp. hysteresis

1

18 'F

9'F

O-Normal display

E4

Camp. start delay time

O-IOMia

2Mia

F4

Display during defrost

I

=

Last value

0

20-20"C

before defrost

ES

Offset on room temp.

-36-36'F

0

CI

Temperature unit

Celsius="C

Fahr.="F

'C