Page 5 of 40
3-FEATURES
METER -
features
Housing/sensor material
PC or Al / PP wetted part (only PVDF for ATEX certifi ed vers.)
Mechanical installation
2” GAS M (PP fl ange DN80 opt.)
Protection degree
IP67/IP68 (Sensor)
Electrical connection
Internal push connectors
Working temperature
-30 ÷ +70°C; +80°C non-continuous
Pressure
from 0,5 to 1,5 bar (absolute)
Power supply
12Vdc / 20÷30Vdc (2-wires versions) - 24Vdc (4-wires versions)
Power consumption
0,6W (2-wires) - 1,5W (4-wires)
Analog output
4...20mA, max 750ohm (4-wires versions)
Relays output
(4-wire only) n°2 3A 230Vac (n.o.)
Digital communication
M
O
DBUS RTU for 4-wire vers. ; (opt.) HART for 2-wire vers.
Max measure range
max 0.25 ÷ 6m
max 0.40 ÷10m
In case of non perfectly refl ecting surfaces, the maximum distance value will be reduced
Blind distance
0,25m (6m versions) / 0,40m (10m versions)
Temperature compensation
digital from -30 to 80°C
Accuracy
±0,2% (of the measured distance) not better than ±3mm.
Resolution
1mm.
Calibration
4 buttons or via HART / MODBUS RTU
Warm-up
5 minutes typical
LCD Display
Plug-in display/keyboard 4 buttons matrix LCD
Ex-proof
ATEX II 1/2G Ex ia II C T6 Tamb -20 ÷ +60°C