9.2.8.2.3 - DELAY
Position the cursor on DELAY, press ENTER to access.
Set the relay delay activation, from 0 to 99 sec.
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
Default value: 0
UPPER
LOWER
DELAY
FILL./EMPT.
ENABLE/DISABLE
►
05 s
DELAY
9.2.8.2.5 - ENABLE/DISABLE
Position the cursor on ENABLE/DISABLE, press ENTER to access.
Select ENABLE to activate relay threshold.
Select DISABLE to not activate relay threshold.
With the SCROLL button you can select the operation mode.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
Default value: DISABLE
UPPER
LOWER
DELAY
FILL./EMPT.
ENABLE/DISABLE
►
EMPTING
FILLING
►
METER -
advanced confi guration
9.2.8.2.4 - FILL./EMPT
Position the cursor on DELAY, press ENTER to access.
it’s possible to select the mode of pump control (FILLING or EMPTING)
With the SCROLL button you can select the operation mode.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
Default value: EMPTING
UPPER
LOWER
DELAY
FILL./EMPT.
ENABLE/DISABLE
►
DISABLE
ENABLE
►
9.2.8.3 - RL2 DIAGNOSTIC
Position the cursor on RL2 DIAGNOSTIC, press ENTER to access.
If it becomes necessary the METER functional control, it’s possible to ena-
ble the RL2 alarm output function. In this case, enabling the function, RL2
is energized in normal operation (RL2 LED on) and is de-energized (LED
RL2 off, safety alarm) when at least one of the four conditions mentioned
below, shall be verifi ed:
- TEMP. : temperature out of range
- ECHO : no echo is detected
- GAIN : the sensor’s gain exceed the value setted in Max Gain TH (7.3.5)
- DIST. : the measured distance exceed the 120% of the maximum
distance in setup
Select ENABLE to activate relay threshold.
Select DISABLE to not activate relay threshold.
With the SCROLL button you can select the operation mode.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
Default value: DISABLE
when an error occurs, a “!” is fl ashing on the display: press SCROLL to
show a message that indicate what kind of error is present. The METER
automatically returns to RUN mode.
DISABLE
ENABLE
►
RL1 THRESHOLD
RL2 THRESHOLD
RL1 PUMP
RL2 DIAGNOSTIC
►