KOTRON

®

R.F. 2-WIRE

Level Transmitter

®

INSTRUCTION MANUAL AND PARTS LIST

DESCRIPTION

Kotron two-wire level transmitters are designed to measure

either liquid or certain dry bulk media. The transmitter is usu-
ally mounted integrally with the probe.
The 24 V DC 4 mA base current is the supply to the unit.
Changes in the level of the medium change this current
between 4 and 20 mA in the two-wire loop. 
This transmitter is available with a variety of options includ-
ing an analog meter and rigid or flexible probes. This
instruction manual applies to 24 V DC models only.

OPERA

TING PRINCIPLE

The amount of capacitance developed in any vessel, is

determined by the size (surface area) of the probe, the
distance from the probe to its ground reference (e.g. tank
wall), and the dielectric of the medium it is measuring.
If the probe’s mounting position is fixed, and the dielectric
value of the medium is constant, then the amount of
capacitance developed in any vessel becomes dependent
upon the probe’s total surface area.
Adjusting the combination of the probe’s diameter and
length (and of course its proximity to ground) in  any given
application can generate the necessary capacitance
required by the electronic circuitry.
As media rises and falls in the tank, the amount of
capacitance developed between the sensing probe and the
ground also rises and falls. This change in capacitance is
converted into a pulse wave form, proportional to the
change in level. The amplifier then converts the proportion-
al pulse signal into a 4-20 mA output signal.

UNP

ACKING

Unpack the instrument carefully

. Inspect all units for dam-

age. Report any concealed damage to carrier within 24
hours. Check the contents of the packing slip and purchase
order. Check and record the serial number for future refer-
ence when ordering parts.

AGENCY APPROV

ALS

Agency

Approval

A

TEX

II 

1G EEx ia 

II 

C T6, Intrinsically safe

Intrinsically safe:
Class 

I

, Div

. 1, Groups A, B, C & D;

Class 

II

, Div

. 1, Groups E, F & G;

FM/CSA

Class 

III

CSA approval only valid with insulated probes.

Explosion proof:

CSA

Class 

I

, Div

. 1, Groups C & D;

Class 

II

, Div

. 1, Groups E,F & G;

Consult factory for proper selection data.

Summary of Contents for Kotron RF 2-Wire Series

Page 1: ...dent upon the probe s total surface area Adjusting the combination of the probe s diameter and length and of course its proximity to ground in any given application can generate the necessary capacita...

Page 2: ...elect code 0 or 4 in housing selections HOUSING IP66 OUTPUT SIGNAL 3 4 to 20 mA output direct action 4 20 to 4 mA output reverse action 0 3 4 NPT cable entry aluminium 1 NPT with local indicator 1 M20...

Page 3: ...tory In all cases a good electrical connection must be made between the ground surface and the probe housing MOUNTING Two wire transmitters with probes up to and including 305 mm 12 in length are ship...

Page 4: ...shing off probe 9 While holding probe cable loosen upper packing gland nut 10 Pull excess cable up through packing gland nut until cable is taut 11 Tighten the packing gland nut 12 Cut off cable 35 mm...

Page 5: ...r bracket The meter is attached by two wires to the terminal block underneath it Pull meter gently out of the housing and lay the meter to one side being careful not to disturb the wiring See Figure 6...

Page 6: ...ailable to measure loop current a If the LED goes completely out proceed to step 4 b If the LED doesn t go out check the following the meter is properly connected the appropriate meter range has been...

Page 7: ...until the loop current is exactly L2mA Calibration is now complete CALIBRATION PROCEDURE A 1 Move the material in the vessel to its L0 0 level 2 Turn the zero coarse zero ne and the ne span calibratio...

Page 8: ...n controls incorrectly set Turn span potentiometers fully clockwise before calibrating zero c Excessive probe capacitance Maximum zeroing range is 450 pf zero dip switch 1 in closed position 650 pf ze...

Page 9: ...chart 1 on page 5 Reduce loop resistance or Increase supply voltage consult factory 4 Loop current less than 4 mA a Incorrect calibration Recalibrate unit b Material level below 0 No corrective actio...

Page 10: ...ard Base Mounting bracket Pipe nipple Bushing O ring Cover Cover assembly O ring Meter assembly Base Description Speci cation Supply Voltage 14 to 40 V DC Current 38 mA max Line Variation Less than 0...

Page 11: ...ptional Mounting Flange Optional Mounting Flange 10 375 13 50 16 625 10 375 13 50 16 625 321 12 65 118 4 63 76 3 00 Probe 102 4 00 10 375 127 5 00 13 50 16 625 Probe 102 4 00 10 375 127 5 00 13 50 16...

Page 12: ...it is essential that a Return Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is avail able throug...

Reviews: