14
EN
WARNING
Definition of warning signs:
Indication that a risk of electrical origin exists.
Indication that a risk exists for the machine or its operation.
Directions to be used only by qualified professionals.
Disconnect electrical power before working on the unit!
2
DESCRIPTION
2.1 OPERATING PRINCIPLE
Sanicondens® Pro/Eco
contains a pump. The tank of the
SANICONDENS® Pro/Eco
has a built-in a float which
controls the operation of the motor. When the condensate enters the tank, the pump starts up.
Sanicondens® Pro
has also a built-in secondary float that can trigger an alarm (audible and/or visual).
2.2 TECHNICAL DATA
Type
CD 10
Sound level
< 45 dBA
Max. vertical pumping
4.5 m
Average operating temperature
35°C
Maximum flow rate
380 L/h
Maximum allowable temperature
80°C
S3 15% (1min30 ON/8min30 OFF)
Min. pH
2.5
Level ON/OFF
56 mm / 46 mm
Weight of the unit
2 kg
Voltage
220-240 V
Tank volume
2.2 L
Frequency
50 Hz
Supply cable
1.5 m
Current consumption
0.52 A
Discharge hose
5 m, Øint: 10mm
Power rating
60 W
Alarm cable (2 cores) (
Pro
)
1.5 m
Electrical class
I
Max. power for the connected boiler gas: 50 kW / oil: 30 kW
Protection index
IP20
Wall mounting
Yes
2.3 LIST OF PARTS SUPPLIED
see pg. 6.
2.4 DIMENSIONS
see pg. 9.
2.5 PERFORMANCE CURVES
see pg. 11.
2.6 VERTICAL PUMPING/HORIZONTAL PUMPING
see pg. 11.
1
AREA OF APPLICATION
Sanicondens® Pro/Eco
is a pump used to lift condensation water from an air conditioning system, a condensation
boiler, dehumidifiers or from refrigeration units. If necessary, insert a neutralisation device (see your boiler manufacturer's
instructions). The use of a neutraliser is mandatory on oil boilers in order to preserve the pump.
The pump starts automatically and has a high level of performance, safety and reliability as long as all the installation and
maintenance instructions mentioned in this manual are strictly followed.
All applications other than those described in this manual are prohibited.
3
START UP
3.1 INSTALLATION
Always install the pump:
– horizontally, using a leveling tool,
– as close as possible to the appliance keeping in mind that the condensate has to drain through gravity into
the pump.
To ensure proper ventilation of the motor, the pump must be free of any obstruction.
The pump can be mounted against a wall using the plastic anchors
A
and screws
B
supplied (accessory bag). See fig.
1
and
2
.
Check that the
Sanicondens® Pro/Eco
is leveled: fig.
2
.
3.2 HYDRAULIC CONNECTION
Connecting the inlet
The pump has two inlets Ø28 mm that can be used as required (fig
3
):
– The left inlet is open.
– The right inlet is protected by a break-off plug. To use the right inlet, first cut out the cut-off plug with a cutter and
remove it.
Drain the condensate water to any of these inlets (fig
4
). If necessary, use a rubber flexible adapter
C
.