Changing the sensor system
There are different probe models for the
EX-TEC® SNOOPER H
for
various points in the pipework system:
manual probe with spiral cable
flexible swan-neck (245 mm long)
rigid probe extension (525 mm long)
The probes can be exchanged or extended in any required
combination.
Changing probes or sensors
switch off the detector and undo the sensor cap (item 5)
remove the sensor from its base with the extraction tool
straighten any bent sensor connections with the extraction tool
replace the sensor in the appropriate probe or base
replace the sensor cap (item 5)
replace the probe in the detector (ensuring that the position of
the connection pins is correct)
tighten the clamping nut
☞
We recommend carrying out an adjustment after
every change of probe or sensor !
flexible mini swan-neck with sensor (145 mm long)