MEASURING  AN  INSULATOR

 

When

 

measuring

 

insulator,

 

there

 

are

 

a

 

few

 

things

 

to

 

consider:

 

1-

 

Most

 

insulators

 

collect

 

dust

 

and

 

get

 

contaminated

 

over

 

time

 

with

 

a

 

mixture

 

of

 

Moisture,

 

rain,

 

dirt

 

etc...

 

2-

 

These

 

matters

 

lower

 

the

 

resistance

 

of

 

the

 

insulator

 

as

 

they

 

are

 

in

 

parallel

 

with

 

the

 

insulator

 

resistance.

 

3-

 

It

 

is

 

recommended

 

to

 

measure

 

the

 

insulator

 

first

 

without

 

the

 

guard

 

to

 

verify

 

that

 

the

 

total

 

resistance

 

is

 

high.

 

Should

 

the

 

total

 

resistance

 

not

 

be

 

high,

 

that

 

could

 

mean

 

that

 

the

 

amount

 

of

 

dirt

 

on

 

the

 

surface

 

of

 

the

 

insulator

 

is

 

too

 

high

 

and

 

therefore,

 

the

 

insulator

 

may

 

require

 

cleaning.

 

4-

 

Should

 

your

 

insulator

 

require

 

cleaning,

 

follow

 

the

 

procedures

 

recommended

 

by

 

it's

 

manufacturer.

 

5-

 

For

 

Final

 

Test

 

and

 

Measurement,

 

use

 

the

 

Guard

 

so

 

that

 

leakage

 

surface

 

current

 

is

 

collected

 

and

 

Insulator

 

is

 

intrinsically

 

tested.

 

The

 

insulator

 

must

 

not

 

be

 

connected

 

to

 

any

 

live

 

component

 

or

 

power

 

source.

 

Use

 

a

 

tied

 

copper

 

wire

 

around

 

the

 

insulator

 

at

 

about

 

its

 

center

 

to

 

connect

 

the

 

guard.

 

 

FIRST  MEASUREMENT

 

MEASURE

 

WITHOUT

 

THE

 

GUARD

 

TO

 

TAKE

 

EVERYTHING

 

INTO

 

ACCOUNT

 

AND

 

FIND

 

OUT

 

IF

 

NEED

 

CLEANING.

 

 

 
 

DIRTY

 

INSULATOR

 

ELECTRICAL

 

EQUIVALENT

 

CIRCUIT

 

DIRTY

 

INSULATOR

 

SECOND

 

MEASUREMENT

 

MEASURE

 

WITH

 

THE

 

GUARD

 

TO

 

ENSURE

 

INSULATOR

 

IS

 

CORRECT.

 

TYPICAL

 

TEST

 

 

LINE

 

LINE

 

 
 
 

LEAKAGE

 

DUE

 

TO

 

CONTAMINATION

 

LINE

 

 
 
 

LEAKAGE

 

 
 

GUARD

 

 

INSULATOR

 

INSULATOR

 

 
 
 
 

 

EARTH

 

EARTH

 

RESISTANCE

 

DUE

 

TO

 

CONTAMINATION

 

CAN

 

BE

 

VERY

 

LOW

 

AND

 

LOWER

 

THE

 

TOTAL

 

RESISTANCE.

 

CLEANING

 

PERIODICALLY

 

CNA

 

ALSO

 

REDUCE

 

SYSTEM

 

POWER

 

CONSUMPTION.

 

 
 

-21-

 

EARTH

 

Summary of Contents for 6213A-IN

Page 1: ...itales VDC GigaOhmios 6213 IN SEW manual ingles www viaindustrial com Medidores de aislamiento Megohmetros Digitales VDC GigaOhmios 6213 IN SEW manual ingles www viaindustrial com 6213A IN DIGITAL VAR...

Page 2: ...ingles www viaindustrial com TABLE OF CONTENTS Index 2 Front Panel Layout 3 Inside Lid Instructions 4 Safety precautions 5 8 Overview 9 Features 10 Connections 11 Specifications 12 Functions 13 15 Sp...

Page 3: ...AYSREADUSER SMANUALBEFOREOPERATINGTHISINSTRUMENT Useonlyonde energisedandisolated disconnectedsystem DONOTPROCEEDIFVOLTAGEPRESENT Checktestleadsfordefects Ifanycracksordamages replacewithnewtest leads...

Page 4: ...AR WARNING Thisinstrumentshould notbeusedinexplosive orinflammable environments although thereisunlikelytobea firehazardfromthe instrumentitself However arcingin faultyinsulation sparkingcausedwhen ma...

Page 5: ...or test leads Preparations for testing of power system grounding or close to it can leave personnel vulnerable to exposure caused by faults at or fed from the system under test transferred potentials...

Page 6: ...hey were new Always disconnect the test leads when changing the batteries by removing the cover which give access to the batteries Always double check the lead connections before making any measuremen...

Page 7: ...warning features should your Variable High Voltage Digital Insulation Meter be connected to a live system 1 3 Never open your Variable High Voltage Digital Insulation Meter except for battery replacem...

Page 8: ...gaOhmios 6213 IN SEW manual ingles www viaindustrial com 1 7 Your Variable High Voltage Digital Insulation Meter has a live circuit warning beeper If It is connected to a live circuit a rapid pulsatin...

Page 9: ...his bar graph is showing voltage output during the first 30 seconds of the test or during automatic discharge of circuits During the automatic discharge of the circuit tested the bar graph displays th...

Page 10: ...6 5KV 7KV 7 5KV 8KV 8 5KV 9KV 9 5KV 10KV Calculate Dielectric Absorption Ratio DAR Automatically Calculate Polarization Index PI Automatically Insulation resistance Auto Ranging on all ranges TM Bar g...

Page 11: ...Ohmios 6213 IN SEW manual ingles www viaindustrial com Medidores de aislamiento Megohmetros Digitales VDC GigaOhmios 6213 IN SEW manual ingles www viaindustrial com 4 CONNECTIONS INSULATOR HV 10kV VAR...

Page 12: ...5KV 5KV 10KV Measuring Range 800K 500G AUTO RANGING Accuracy 5 2 digits Power 8 x 1 5V Alkaline batteries Output Power Limit 1W Voltage Regulation Selected Voltage 20 5 of nominal value unless curren...

Page 13: ...test voltage press 10KV button 2 6 3 Insulation Resistance Measurement 5KVdc To Select 5KVdc test voltage press 5KV button 4 6 4 Insulation Resistance Measurement 2 5KVdc To Select 2 5KVdc test volta...

Page 14: ...certain time or to make comparison See Special Features for more Timer Functions 6 11 STOP test To stop the test in progress press the TEST button 3 The test will immediately stop discharge and the i...

Page 15: ...ed by a one second long beep accompanied by the HOLD message on the display DO NOT REMOVE LEADS UNTIL THE HOLD MESSAGE APPEARS ON THE DISPLAY 6 15 Replace Battery Warning Indicator If the battery ener...

Page 16: ...Polarization Index The Polarization Index or PI is the ratio of the Insulation Resistance measured at 10 Minutes divided per the Insulation Resistance measured at 1 Minute 10 Minutes after starting a...

Page 17: ...t any time before during and after the test It s your responsibility to ensure proper contact of the leads at all times Once a test is finished the testers will automatically discharge capacitive or i...

Page 18: ...6213 IN SEW manual ingles www viaindustrial com 8 PREPARATION FOR MEASUREMENT 8 1 Before testing always check the following At Power ON read the display to make sure the Replace Battery message is no...

Page 19: ...ng care to observe correct polarity Replace battery cover 9 2 Cleaning Storage Periodically wipe the case with a damp cloth and detergent Do not use abrasives or solvents If the meter is not to be use...

Page 20: ...are not live before commencing testing Secure both test leads properly to the insulation to test and use guard lead to collect surface leakage Good contacts are necessary to avoid flashing at high vol...

Page 21: ...surface of the insulator is too high and therefore the insulator may require cleaning 4 Should your insulator require cleaning follow the procedures recommended by it s manufacturer 5 For Final Test a...

Page 22: ...r characteristics may deteriorate due to many factors Their material properties may deteriorate with time and frequency use as well as stress put on to them One of the factor we will be testing is the...

Page 23: ...ormers are painted or dipped with insulating varnish large power transformers are painted with High Voltage insulating paint of very high specifications Many Applications uses insulating material to p...

Page 24: ...arranty does not apply to any of our products which have been repaired or altered by unauthorized persons in any way so as in our sole judgement to injure their stability or reliability or which have...

Reviews: