Manual – MOVIAXIS® MMD60B - Functional Safety
3
Requirements on the external safety controller
Safety Conditions
3.3.1
Sample circuit "safety relay"
The following figure shows the basic interface of an external safety relay (according to
the before mentioned requirements) to MOVIAXIS
®
MMD60B.
The information in the respective manufacturer's data sheets must be observed for
connection.
2466502411
[1] Safety relay
[4] STO signal
[2] DC 24 V voltage supply
[5] Reset button for manual reset
[3] Fuses in accordance with the manufacturer's
specifications of the safety relay
[6] Permitted emergency stop actuating device
[4]
[3]
[1]
[5]
[6]
[2] U