Manual – MOVIAXIS® MMD60B - Functional Safety
15
3
Requirements on startup
Safety Conditions
3.4
Requirements on startup
• To validate the implemented safety functions, they must be documented and
checked after successful startup (validation).
Observe the limitations for safety functions in chapter "Limitations" for the validation
of the safety functions. Non-safety-relevant parts and components that affect the
result of the validation test must be deactivated, if necessary.
• For using MOVIAXIS
®
MMD60B in safety-related applications, it is essential that you
perform and record startup checks for the disconnecting device and correct wiring.
3.5
Requirements on operation
• Operation is only allowed within the limits specified in the data sheets. This applies
both to the external safety relay as well as MOVIAXIS
®
MMD60B.
• You must check the safety functions on a regular basis to ensure proper functioning.
The test intervals should be specified in accordance with the risk analysis.