SETRONIC Verona
33
Observe the interference values (DETEC) for at least a couple of minutes
and set the threshold for a figure above the highest peak read.
NOTE: The following possible threshold values can be selected: 200, 284, 371, 461, 581, 673,
752, 825, 914, 984, 1066, 1137, 1219, 1280, 1383, 1462.
Detec: 0
Fire : 461
In the first line the interference figure is shown in
real time.
The second line shows the fire threshold, with
default of 461. With the keys
it is possible to
increase or reduce this value.
Data not changed
OK to exit
If the threshold stays the same as that already in
memory, the following message appears.
Saving data...
Once the thresholds regulation has been completed,
press OK to save data and return to the previous
menu.
8.3 CONFIGURATION OF THE SYSTEM
Using the System Setup menu you can configure some of the control unit settings:
Set a delay time for fault output 30, 60 or 90 seconds according to the event
that caused it, or have an immediate output;
Set the fault output contact as normally closed or open;
Check if are there any communication errors between the Control unit and the
Detector.