High Temperature Pressure Measurement

:  Possible using a length of piping or a "syphon" to

isolate the instrument from the hot media.  Since there is no flow, the temperature drop along the tubing
is considerable and usually a relatively short length is sufficient to bring the pressure media temperature
within acceptable limits for the instrument.  Alternatively a temperature isolator, part number GA33, can
be fitted (G¼ connection only).  Pressure media must not be allowed to solidify in the tube and/or
pressure port.

ELECTRICAL INSTALLATION

All types include suppression devices providing transient protection to EN 61000-4-2 and EN 61000-
4-4.

For all types conformity with the requirements of the CE mark only applies when
connection is made with Setra Systems approved cable, See APPROVED CABLE
section, and the shield of that cable is connected to a reliable ground point at the
instrumentation end.

Types 540 / 542 Water Submersible Cable (IP68 rated):

  These types are capable of being

immersed to a maximum depth of 200m WG.

Types 540 / 542:

  To combat the effects of lightning strike these types are fitted with suppression

devices providing surge immunity to  IEC 801 Part 5.  To protect the ‘receiving’ equipment it is
recommended the end user fits a Lightning Protection Unit (LPU) at the instrumentation end close to the
point of cable entry into the building, installed as recommended by the LPU manufacturer, to protect
against the likely high current surge resulting from lightning strikes.

Types 540 / 542 Weatherproof Cable ( IP66):

  These types employ a weatherproof (IP66 rated)

cable assembly.

Types 540 / 541 / 542 10-6 Bayonet Connector:

  These types are fitted with a MIL-C size 10,

6 pin receptacle.  The mating socket (not supplied) must conform to MIL-C-00264872.

APPROVED CABLES

Setra Systems uses cable comprising 6  color-coded wires, with a central vent tube, enclosed by an
aluminium/polyester shield where the screen is in intimate contact with a separate drain wire.  The outer
sheath can be of various material, depending upon application and operating temperature, e.g.  Exar
(non-immersible, +150°C max),  PTFE (non-immersible, +200°C max), Polyurethane (immersible,
+70°C).

OPERATION

Having installed the transducers as instructed they are ready for use. The transducer should not be
removed while the system is at pressure

 Before applying power, check that the correct polarity and

excitation levels are being applied. See 

ELECTRICAL REQUIREMENTS

.

Summary of Contents for 540 Series

Page 1: ...Installation Guide MODELS 540 541 542 Pressure Measuring Transducers 560550 0085 Rev A 1 800 257 3872 TOLL FREE 1 978 264 0292 FAX www Setra com Web Site ...

Page 2: ...Setra offers a complete line of products for these industries Industrial HVAC Test Measurement Barometric Ultra High Purity Sanitary ...

Page 3: ...LE section All instruments conform to the appropriate specifications and or drawings applicable and have been subjected to relevant strict quality control procedures HAZARDOUS PRODUCTS The Consumer Protection Act of 1987 Section 6 of the Heath and Safety at Work Act 1974 and the Control of Substances Hazardous to Health Regulations 1988 require that we advise recipients and users of our products o...

Page 4: ...UNDER NO CIRCUMSTANCES be allowed to touch the pressure sensitive diaphragm Pressure couplings should be sealed against the outer face at the pressure port entry using bonded seal washer such as Part Number Description Dowty Ref GA29 G bonded seal up to 100 C operation 400 021 4490 02 GA30 G bonded seal up to 200 C operation 300 021 0967 02 GA31 G1 8 bonded seal up to 200 C operation 300 020 0967 ...

Page 5: ...ression devices providing surge immunity to IEC 801 Part 5 To protect the receiving equipment it is recommended the end user fits a Lightning Protection Unit LPU at the instrumentation end close to the point of cable entry into the building installed as recommended by the LPU manufacturer to protect against the likely high current surge resulting from lightning strikes Types 540 542 Weatherproof C...

Page 6: ...e CALIBRATION Transducers are calibrated to the datum requested at time of order this can be identified as follows Code G gauge datum vented to atmosphere via the electrical connection Code A absolute datum Code S sealed reference reference side of the instrument is sealed and the output electrically adjusted to zero with 1013 mb applied to pressure port Code U uni directional differential Code B ...

Page 7: ...n 50V d c for this test Causes of Failure Excess pressure of more than twice the rated range 1 5 times rated range for Inconel wetted parts versions A short duration pressure cycle having such a peak value may be sufficient to damage the strain gauge The instrument may withstand some excess pressure without failure but a change in residual output may result If this is not excessive the instrument ...

Page 8: ...Setra Systems with the following 1 Name and phone number of person to contact 2 Shipping and billing information 3 Full description of malfunction 4 Remove any pressure fitting and plumbing that you may have installed and enclose any required mating electrical connectors and wiring diagrams Please ship to Setra Systems at the address shown below or to your local Setra Distributor when a replacemen...

Page 9: ... INSTRUMENT CONTAINS VITON W A R N I N G ELECTRICAL REQUIREMENTS SUPPLY VOLTS MODEL E LECTRI CAL C ODE MAX RATED OUTPUT ve SUPPLY ve SUPPLY ve OUTPUT ve OUTPUT CASE EARTH 540 541 5 42 B3 Pin A Pin D E Pin B Pin C F 541 542 N4 Red White Yellow Blue Shield 541 542 UA Red White Yellow Blue Shield 541 B4 15V d c 10V d c 0 30mV at rated supply Pin 1 Pin 4 Pin 2 Pin 3 Pin 5 B3 10 6 Bayonet Connector N4 ...