Load Trap
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load
traps include the reported input load, load status, Location of the Sentry, and identifier and name of the
affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Load returns to a non-error status.
Load traps
Status Error Description
Normal
Infeed is on and within preset thresholds
NotOn
Infeed is off
Reading
Non-error state – Load status currently being read
LoadHigh
x
Infeed current load exceeds preset threshold
OverLoad
x
Infeed current load exceeds the measurable range for the infeed
ReadError
x
Unable to read Load status
NoComm
x
Communication to the infeed has been lost
Configuring Traps
SNMP Trap Command Summary
Command Description
Set Trap Tower Status
Enables or disables the Tower Status trap
Set Trap Infeed Status
Enables or disables the Infeed Status trap off
Set Trap Infeed Load
Enables or disables the Infeed Load trap
Set Trap Infeed HighThresh
Sets the Infeed Load trap high limit
Set Trap Outlet Change
Enables or disables the Outlet Change trap
Set Trap Outlet Status
Enables or disables the Outlet Status trap
Show Traps
Displays trap configurations
Enabling or Disabling a Status trap
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.
To Enable or Disable a Status trap:
At the Sentry: prompt, type
set trap
(
tower
,
infeed
, or
outlet
)
status
, followed by the tower, infeed or
outlet name, and
on
or
off
.
Press
Enter
, or
Type
set trap
(
tower
,
infeed
, or
outlet
)
status all
, followed by
on
or
off
and press
Enter
.
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
Sentry: set trap tower status .a on<Enter>
The following command enables the Status trap for the tower named Florida_HQ_1:
Sentry: set trap tower status Florida_HQ_1 on<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet
Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is
disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.