38
38
6 Technical Parameters
Table6-1
Technical parameters
Parameters
PV Input (DC)
Maximum PV array power(w)
6000
Vmax PV
(
V
)
580
Rated voltage
(
V
)
360
Maximum input current(A)
13/13
Isc PV(V)
14/14
MPPT voltage range
125-550
Number of MPPT trackers
2
Battery input and output
Battery voltage range
(
V
)
40-58
Rated battery voltage
(
V
)
48
Rated charging/ discharging power(W)
4200/5000
Maximum charging/discharging current(A)
70/100
BMS communication interface
CAN/RS485
Reverse polarity protection
YES
Grid Input/Output parameters
Grid rated apparent power
(
VA
)
5000
Grid rated voltage
(
V
)
220/230Va.c.
Grid connection
1/N/PE
Grid rated frequency
(
Hz
)
50/60
Grid rated current
(
A
)
21.7
Grid maximum current
(
A
)
22.8
Overcurrent protection(A)
26
Short circuit current(A)
129Apeak, 8.5Arms
Power factor range
0.8 ahead~0.8 behind
Total harmonic distortion
(
THD,
rated power
)
<3%