MODEL: R1M-A1

Remote I/O R1M Series

CONTACT INPUT MODULE

(contact input, 32 points)
Functions & Features
• 32-point dry contact inputs
• Easy system expansion via Modbus RTU
• CE marking

40
(1.57)

115

(4.53)

mm (inch)

175 (6.89)

MODEL: R1M-A1[1]-[2]

ORDERING INFORMATION

• Code number: R1M-A1[1]-[2]
Specify a code from below for each [1] and [2]
(e.g. R1M-A1T-M2)

[1] FIELD TERMINAL TYPE

T: M3 screw terminals
C1: FCN type connector (No CE conformance)

[2] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable (model: FCN32)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC.  Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.

GENERAL SPECIFICATIONS

Connection
  Power input, transmission: Euro type connector terminal

  RS-232-C: 9-pin D-sub connector (male)
  (Lock screw No. 4-40 UNC)
  I/O: M3 screw terminals or FCN type connector
Isolation: Input to RS-232-C or RS-485 to power
Count memory at power loss: Count value is not saved
when the power supply is lost.
Node address setting: Rotary switch; 1 – F (15 nodes)
RUN indicator LED: Green light blinks in normal conditions.

COMMUNICATION

Baud rate: 38.4 kbps
Communication: Half-duplex, asynchronous, no procedure
Protocol: Modbus RTU
Refer to Modbus Protocol Reference Guide (EM-5650) for
supported functions.
■ RS-232-C
Standard: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
■ RS-485
Standard: Conforms to RS-485, EIA
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S
0.9 dia.)

INPUT SPECIFICATIONS

Input: Dry contact, 32 points
Commons: All negatives
Sensing: Approx. 5 V DC (pull-up resistance 22 kΩ)
≤ 1.5 V at ON
≥ 4 V at OFF
Sampling rate: 50 msec.
• Totalizing Counter Function
Number of input channels: 16
(ch.1 thr. 16 available both with instantaneous status and
totalized value)
Max. input frequency: 100 Hz
Minimum pulse width: 5 ms
Counter reset input: Pulse rising (ch.32 assigned)
Max. counter value: 999 999 999 (reset to zero at overflow)

INSTALLATION

Power consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lbs)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M-system R1M Series

Page 1: ...ss Count value is not saved when the power supply is lost Node address setting Rotary switch 1 F 15 nodes RUN indicator LED Green light blinks in normal conditions COMMUNICATION Baud rate 38 4 kbps Co...

Page 2: ...Reinforced insulation 300 V Input to RS 232 C RS 485 Basic insulation 300 V EXTERNAL VIEW RS 485 Connector Power Terminals Node Address Setting Rotary SW Configurator Jack RUN Indicator LED RS 232 C 9...

Page 3: ...Shielded Twisted pair Cable To Other PC Recorders Jumper FG U V POWER D SUB CONNECTOR 9 8 7 6 5 4 3 2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 29 30 31 32 33 35 34 36 ch 1 ch 2 ch 3...

Page 4: ...ngle Registers X General purpose register within the slave 07 Read Exception Status 08 Diagnostics 09 Program 484 10 Poll 484 11 Fetch Comm Event Counter Fetch a status word and an event counter 12 Fe...

Page 5: ...pe J3 0 No burnout 1 Upscale 2 Downscale 4 I 16 bit integer F 32 bit floating B16 16 byte character 1 Discrete output only 2 Thermocouple input only 3 Trigger contact input for Types GH2 and J3 Only A...

Page 6: ...E A D DATA Decimal DC 20V 20000 5V 5000 1V 10000 0 8V 8000 0 2V 20000 50mV 5000 10mV 10000 Thermocouple Temperature x 10 RTD Temperature x 10 Potentiometer 0 100 2000 0 500 0 1k 0 10k BIT NAME DESCRIP...

Page 7: ...CRC 270 to 1000 C 0X13 J IC 210 to 1200 C 0X14 T CC 270 to 400 C 0X15 B RH 100 to 1820 C 0X16 R 50 to 1760 C 0X17 S 50 to 1760 C 0X18 C WRe 5 26 0 to 2320 C 0X19 N 270 to 1300 C 0X1A U 200 to 600 C 0...

Page 8: ...6 1 81 DIN RAIL 35 mm wide FCN TYPE CONNECTOR T1 T2 T3 T4 T5 T6 T7 104 4 09 10 39 105 4 13 14 55 163 6 42 165 6 50 175 6 89 3 5 20 dia MTG HOLES FOR WALL MOUNT FCN TYPE I O CONNECTOR 6 24 40 1 57 40 1...

Page 9: ...istance between the PC and the R1Ms is long insert an RS 232 C RS 485 Converter for isolation RS 232 C RS 232 C RS 485 Converter model R2K 1 Specifications are subject to change without notice Ruggh l...

Page 10: ...ed to the unit and TDK Model ZCAT3035 1330 or equivalent for the RS 232C cable are recommended The equipment must be installed such that appropriate clearance and creepage distances are maintained to...

Page 11: ...ith the attached jumper pin or with a leadwire When the device is not at the end remove the jumper pin Power Circuit Shielded Twisted pair Cable To Other I O Modules Jumper FG U V POWER D SUB CONNECTO...

Page 12: ...tor is used when the device is at the end of a transmission line 2 Install shielded cables to all sections and ground them at single point 2 FG RS 485 CHECKING 1 Terminal wiring Check that all cables...

Page 13: ...W TERMINALS FCN TYPE CONNECTOR T1 T2 T3 T4 T5 T6 T7 104 4 09 10 39 105 4 13 14 55 163 6 42 165 6 50 175 6 89 3 5 20 dia MTG HOLES FOR WALL MOUNT FCN TYPE I O CONNECTOR 6 24 40 1 57 40 1 57 Connector P...

Reviews: