Instructions for installation and use
p. 9/34
4. Installation
4.1. Installing the sauna control unit
Note
Fig. 1
(figures chapter)
Observe the following points when installing the sauna control unit:
●
The sauna control unit must be installed outside the sauna room or in accord-
ance with the recommendation issued by the sauna manufacturer.
●
The ambient temperature must be within a range spanning -10 °C to +40 °C.
●
The sensors may only be connected using the sensor wires provided with the
unit, which are heat-resistant up to 150 °C.
ATTENTION!
Damage to the unit
The sauna control unit is protected against jets of water, however direct contact
with water could still damage the unit.
●
Install the sauna control unit in a dry place at which a maximum humidity of
95% is not exceeded.
The sensor wires may be extended under the following conditions:
●
When a silicon wire resistant to temperatures up to 150 °C is used.
●
The minimum cross-section of the wire is 0.5 mm
2
.
●
The length of the heater sensor wires may NOT exceed 10 m.
ATTENTION!
Sources of interference can have a negative effect on signal transmission
●
Lay all sensor wires separately from other mains wires and control wires.
●
Protect wires with only one layer of insulation by using a pipe (double insulation).