Instructions for installation and use
p. 6/44
2.2. Safety information for the installer
● Installation may only be performed by a qualified electrician or
similarly qualified person. Work on the sauna control unit may
only be performed when the power has been disconnected.
●
An all-pole disconnecting device with full cut-off compliant with
overvoltage category III must be fitted on-site.
●
The sauna control unit must be installed outside the sauna room
at a height of approx. 1.70 m or in accordance with the rec-
ommendation issued by the sauna manufacturer. The ambient
temperature must be within a range spanning -10 °C to +40 °C.
●
The heater sensor must be attached in a way that it is not af-
fected by a flow of air.
●
The heater supply cable must have a minimum cross-section of
2.5 mm
2
and be temperature resistant up to 150 °C.
●
Also comply with the regulations applicable at the installation
location.
●
For your own safety, consult your supplier in the event of prob-
lems that are not explained in sufficient detail in the installation
instructions.