INPUT REGISTERS

 (See 

Table 1

 

Modbus register maps

)

The input registers are read-only. 

Table 1

 shows how the data is organized in the 

input register sector. The measured data starts from address 1 (30001) and ends at 
address 14 (30014). The other input registers are not used. When they are addressed, 
they return ‘0’.

All the data can be read by “Read Inputs Registers” command. 

Table 1

 shows 

what the type of the returned data for each register is and the way it should be 
interpreted. For example reading ‘300’ in input register 1 means that the measured 
analogue input signal is 3,0 VDC (or 6,0 mA), reading ‘50’ in input register 2 means 
that the output voltage is 50 % Us (115 VAC).

 

 

Input register 1

 (30001) shows the current value of measured analogue input 

signal. This value depends on the selected analogue input type. When voltage 
input is selected, the values vary in the range of 0—1.000 (0—10,0 VDC). When 
current input is selected, the values vary in the range of 0—1.000 (0—20,0 mA).

 

 

Input register 2

 (30002) shows the current value of the output voltage. This input 

register is overridden by holding register 31 if output override control (holding 
register 8) is enabled. When output override control is disabled, this input register 
shows the value of the output voltage according to the selected operating mode. 
The output voltage values vary in the range of 30—100 % Us (69—230 VAC). 
Reading ‘0’ (0 VAC) indicates that the controller is off. 

 

 

Input register 3

 (30003) shows the type of the analogue input signal. This input 

register is defined by holding register 11 or by the hardware setting of position 4 
of the DIP switch. The values are ‘0’ (for 0—20 mA) or ‘1’ (for 0—10 VDC)

 

 Input register 4

 (30004) shows the selected mode of the analogue input. This input 

register is defined by holding register 12 or the hardware setting of position  1 of 
the DIP switch (

Fig. 4

), according to the selected operating mode. The values are 

‘0’ (for descending mode) or ‘1’ (for ascending mode).

 

 

Input register 5

 (30005) shows the value of the maximum output voltage. This 

input register is defined by holding register 13 or the hardware setting of the Max. 
trimmer (

Fig. 6

), according to the selected operating mode. The register values are 

in range of 75—100 (75— 100 % Us VAC).

 

 

Input register 6

 (30006) shows the value of the minimum output voltage. This 

input register is defined by holding register 14 or the hardware setting of Min. 
trimmer (

Fig. 7

), according to the selected operating mode. The register values 

are in range 30—70 % Us.

 

 

Input Register 7

 (30007) gives information about the OFF level state. In Standalone 

mode it contains the value set by position 2 of the DIP switch (

Fig.  4

). In Modbus 

mode it contains the value of holding register 15. It could be ‘0’ (disabled) or ‘1’ 
(enabled).

 

 

Input Register 8

 (30008) gives information about the OFF level value. In Standalone 

mode it contains the value set by the OFF level trimmer (

Fig. 8

). In Modbus 

mode it contains the value set by holding register 16. This value depends on the 
selected analogue input type and mode. The register values can vary from 0 to 40 
(0— 4,0  VDC / 0—8,0 mA) and from 60 to 100 (6,0—10,0 VDC / 12,0— 20,0  mA). 
The values depend on the selected analogue input type and mode.

 

 

Input Register 9

 (30009) gives information about the kick start or soft start 

selection. In Standalone mode the value corresponds to the start type set by 
position 3 of the DIP switch. In Modbus mode it contains the value set by holding 
register 17. The register values are ‘0’ (for soft start) or ‘1’ (for kick start).

 

 

Input Register 10

 (30010) shows the state of the remote control input. When it 

is disabled, the unit works in normal operating mode. When the remote control 
input is enabled, the controller is in stand-by mode. The register values are ‘0’ (for 
disabled) or ‘1’ (for enabled).

 

 

Input Register 12

 (30012) shows the status of the unregulated output L1. When 

the analogue input signal is below the value of the OFF level (if enabled) or when 
the remote control input is disabled, the output voltage of the unregulated output 
L1 is ‘0’ = OFF (0 VAC). Otherwise it is ‘1’ = On (230 VAC)

EVS

ELECTRONIC FAN SPEED  
POWER MODULE WITH MODBUS RTU 

Summary of Contents for EVS Series

Page 1: ...Mounting and operating instructions EVS ELECTRONIC FAN SPEED CONTROLLER ...

Page 2: ...ECHNICAL DATA 4 STANDARDS 5 WIRING AND CONNECTIONS 5 OPERATIONAL DIAGRAMS 6 MOUNTING INSTRUCTIONS IN STEPS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 OPERATING INSTRUCTIONS 11 MODBUS REGISTER MAPS 12 TRANSPORT AND STOCK KEEPING INFORMATION 16 WARRANTY INFORMATION AND RESTRICTIONS 16 MAINTENANCE 16 EVS ELECTRONIC FAN SPEED POWER MODULE WITH MODBUS RTU ...

Page 3: ...r condensation spots All installations shall comply with the local health and safety regulations and local electrical codes This product can only be installed by an engineer or a technician who has an expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is life Always disconnect the power source before connecting th...

Page 4: ...ge 0 10 VDC 10 0 VDC current 0 20 mA 20 0 mA Analogue input modes ascending or descending Analogue input functionality Normal mode Logic mode Remote control input normal or timer functionality Regulated output 30 100 Us Max output load depends on the version Unregulated output L1 230 VAC 50 60 Hz max 2 A Min output voltage setting Umin 30 70 Us 69 161 VAC selectable by trimmer or via Modbus Max ou...

Page 5: ...N Neutral PE Earth terminal L1 Unregulated output 230 VAC max 2 A U1 U2 Regulated output to the motor SW Remote timer switch A Modbus RTU RS485 signal A B Modbus RTU RS485 signal B V Supply output 12 VDC 1 mA Ai Analogue input 0 10 VDC 0 20 mA or 10 0 VDC 20 0 mA Logic input Timer functionality min 2 5 VDC and 30 ms GND Ground Connections Cable cross section max 2 5 mm2 Cable gland clamping range ...

Page 6: ...10 VDC 20 mA 6 VDC 12 mA U out 100 75 70 30 Umax range Umin range Off level Off level enabled Ascending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin Descending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin t s Umax Umin 0 Ai 10 VDC 20 mA Uout 100 75 70 30 0 VDC 0 mA Umax range Umin range Kick start time t s Umax Umin 0 Ai 10 VDC 20 mA Uout 1...

Page 7: ...level Timer mode Logic mode 0 t s 5 VDC 2 5 VDC Remote Switch VDC Stand by Operate Voltage amplitude range Switch control signal t s 0 Uout 100 75 Umax range Kick start time Operation timer Controller is off Kick start enabled Soft start enabled t t t t SW ON ON Holding register 18 Holding register 21 Soft start duration Soft start duration Start Output Umax Timer Soft start Stop Start Stop Operat...

Page 8: ...g 2 Mounting dimensions Fig 1 Mounting dimensions Fig 2 Mounting position 140 102 4 x 4 5 0 124 205 92 Acceptable Not acceptable 3 Connect the motor fan 4 Connect L1 output for a 3 wire connection controlled valve etc if necessary See Fig 3b 3 wire motor connection Fig 3 Wiring and connections Power supply 230 VAC 50 60 Hz Remote control switch Modbus RTU A B Analogue input 0 10 VDC 0 20 mA Supply...

Page 9: ... onto the pins If it does not leave the jumper open see Fig 5 Example 1 Example 2 Fig 5 Network bus resistor jumper Slave 1 RX ТX NBT NBT NBT Slave 2 Master Slave n Slave 2 Slave 1 RX ТX NBT NBT Master Slave n ATTENTION If an AC power supply is used with any of the units in a Modbus network the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT USB RS485 converter T...

Page 10: ... minimum speed depending on the analogue input mode ascending descending 5 If OFF level is enabled and descending analogue input mode is selected the motor will stop running 6 Set the analogue input signal to the maximum value of 0 VDC or 0 mA 7 The connected fan will run at minimum speed or maximum speed depending on the analogue input mode ascending descending 8 If OFF level is enabled and ascen...

Page 11: ... otherwise Softstart Kickstart is executed every time the controller is switched on When Timer mode is selected the controller receives a pulse control signal from the remote control switch When Logic mode is selected the controller receives a pulse control signal from the Ai input In both modes Timer mode and Logic mode the pulse width is to be more than 30 ms otherwise the signal is filtered FRO...

Page 12: ...nsigned int Maximum output voltage 75 100 75 100 75 Us 100 Us 6 Minimum output voltage unsigned int Minimum output voltage 30 70 30 70 30 Us 70 Us 7 Enable off level unsigned int Enables off level 0 1 0 1 Disabled Enabled 8 Off level value unsigned int Off level value depending on the selected analogue input type and ascending descending analogue input mode 0 40 60 100 Ascending mode 0 400 0 200 V...

Page 13: ...ble Active only if holding register 7 is set to 1 0 1 0 0 1 Disabled Enabled 16 Off level value unsigned int Off level value Depends on the selected analogue input type and ascending descending analogue input mode Always settable Active only if holding register 7 is set to 1 0 40 60 100 0 Ascending mode 0 40 0 40 Voltage 0 VDC 4 0 VDC Current 0 mA 8 0 mA Descending mode 100 60 100 60 Voltage 10 0 ...

Page 14: ...s are 0 for descending mode or 1 for ascending mode Input register 5 30005 shows the value of the maximum output voltage This input register is defined by holding register 13 or the hardware setting of the Max trimmer Fig 6 according to the selected operating mode The register values are in range of 75 100 75 100 Us VAC Input register 6 30006 shows the value of the minimum output voltage This inpu...

Page 15: ...s Changing these registers you change the communication settings The default Modbus settings are 19200 E 1 as it is stated in the Modbus Protocol Specification The next three registers 4 5 and 6 are read only They contain information about the hardware and firmware versions Holding register 7 40007 sets the operation mode of the controller There are two options Standalone mode and Modbus mode In S...

Page 16: ...ster values can vary from 0 to 200 0 200 seconds This setting is accessible only in Modbus mode The working time is equal to the sum of the kick start soft start duration time and the time value of the operation timer When a working time expires only a remote control input or analogue input can restart the unit The next holding registers 22 40022 30 40030 are not used They are read only Holding re...

Reviews: