RTVS8

115—230 VAC TRANSFORMER FAN SPEED 
CONTROLLER WITH MODBUS RTU COMMUNICATION

Explanation of specific Modbus registers

The unit has factory pre-set parameters written in Modbus map. It can function 
without any other settings. However, there are some special registers you may need 
to set depending on you combination of products. These are listed in 

Table 3

  below.    

Table 3  Voltage steps

Modbus holding 
registers

Description

Values 

Remark

11

Control Set

Automatic control – takes value 

from sensor. Manual Control – 

takes value from register 12

0=Manual mode;

1=Auto Forward mode;

2=Auto Reverse mode

It is possible to change the control of the article only when the switching 

of the current command has finished. 

13

Output Update 

Interval

Time delay to update the output 

in automatic mode

5 s—600 s

If the value of the sensor connected is changing too fast this is the 

register that provides control of the time between two consecutive 

switching.

16

Hysteresis delta

The difference between 

the upwards switching and 

downwards switching step 

percentage

2—10 %

This value is subtracted from the threshold when the article is switching 

from high to low input value. Hysteresis value is 2 – 10%, it means for  

threshold 20%, the “threshold – hysteresis” = 18 % for Δ = 2 %. 

17

Communication 

Lost Output 

State

Set output when Modbus 

communication is lost

OFF;

Last step selected

Set to 0 = OFF, when there is Modbus Timeout set, when the device 

encounters Timeout - RTVS8 enters STOP mode, output is 

0. If the remote sensor is lost – device enters state 0 = OFF. Both 

communications lost, article goes to OFF.

When set to 1 = Last step selected, on Modbus Timeout occurrence and 

sensor is connected – article continues to operate in regarding of the 

input from the sensor, if sensor is lost – the article stays on the last 

step selected. If both communications are lost, device stays on the last 

step selected. 

In Auto modes, if there is no communication to the control/monitoring 

station, the article continues to operate autonomously while the sensor 

is connected.

18

Sensor output 

register value 

number

Select which sensor output will 

be used as input to the device

Digital potentiometer;

Temperature;

Relative Humidity;

CO

2

/CO

2

eq;

CO/TVOC;

NO

2

Sensor output register value number, define which sensor value will be 

taken for control of the device switching. The restrictions that apply 

are for Sentera Sensors only, and the SPV device. When SPV device is 

connected this value becomes automatically 1 and cannot be changed 

until other sensor is connected.

21—25

Input value 

step 1—5

Input value to switch to output 

steps 1—5

Switches to output step X at 

X % input value and steps 

down to output previous step 

at X % - Hysteresis delta 

(HR16) set

Input Value Step X – the steps will be activated over these thresholds. 

If register value is 0 – this step will be skipped as a holding step, but 

it will be used as intermediate step if needed to switch to upper/lower 

step. Minimum difference between steps thresholds is 11%, that way any 

overlapping of the switching and the hysteresis is avoided.

VERIFICATION OF INSTALLATION

Use only tools and equipment with non-conducting handles when working on 
electrical devices.

ATTENTION

Safe operation depends on proper installation. Before start up, ensure the following:

 

The mains supply is connected correctly.

 

Protection is provided against electrical shock.

 

The cables are the appropriate size and fuse-protected.

 

There is sufficient air flow around the unit.

 

ATTENTION

The unit is supplied with electrical energy at voltages high enough to inflict 
personal injury or threat to health. Take the relevant safety measures. 

ATTENTION

Disconnect and confirm that there is no live current flowing to the unit before 
servicing.

 

ATTENTION

Avoid exposing the controller to direct sunlight!

Summary of Contents for RTVS8 Series

Page 1: ...RTVS8 115 230 VAC TRANSFORMER FAN SPEED CONTROLLER WITH MODBUS RTU COMMUNICATION Mounting and operating instructions ...

Page 2: ...BUS RTU COMMUNICATION Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 10 VERIFICATION OF INSTALLATION 12 TRANSPORT AND STORAGE 13 WARRANTY AND RESTRICTIONS 13 MAINTENANCE 13 ...

Page 3: ...ation can affect the product performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electr...

Page 4: ... quality TVOC carbon monoxide or nitrogen dioxide Selection can be made via Modbus holding register 18 For indoor use surface mounted TECHNICAL DATA Supply voltage 115 230 VAC 50 60 Hz Modbus RTU communication TK monitoring function for thermal motor protection Controlled by analogue signal via DADCM Operating modes Automatic from low to high or from high to low Fan speed based on input from exter...

Page 5: ... motor neutral L Regulated output to motor line Pe Protective earth terminal N RELAY Unregulated output that can be set manually ON OFF or automatically via Modbus Holding register 19 and 15 L N INPUT Power supply neutral L Power supply phase 230 VAC 50 60 Hz TK Input TK monitoring for thermal motor protection TK 2 RJ45 master socket to connect a Sentera sensor transmitter for demand based control...

Page 6: ...unting position 3 Pay attention to the following instructions in order to minimize the operating temperature 3 1 Respect the distances both between the wall ceiling and the device and between two devices as shown in Fig 2 In order to ensure sufficient ventilation of the controller clearance on every side has to be maintained 3 2 When installing the device please keep in mind that the higher you in...

Page 7: ...inals A safety isolator disconnect switch should be installed on the mains electricity side of all motor drives ATTENTION Fig 3 Wiring and connections RJ45 master socket to connect Sentera HVAC transmitter or potentiometer RJ45 Gateway to connect PC with 3SModbus software Regulated output to motor Relay output unregulated output NO Contact 115 230 VAC Power supply 115 230VAC 50 60Hz TK monitoring ...

Page 8: ... controller or potentiometer Consult our website for possible combinations 2 Crimp the RJ45 cable for the Modbus Slave connector and plug it into the socket It is used to connect the unit to a PC or another master device for monitoring or manual control via Modbus holding register 12 To do so you will need Sentera s Modbus to USB converter CNVT USB RS485 V2 To modify or monitor parameters of a Sen...

Page 9: ...X ТX NBT NBT Master Slave n On a Modbus RTU network two bus terminators NBTs need to be activated NOTE Do not expose to direct sunlight CAUTION Voltage steps The standard configuration of the output voltages is as indicated in Table 1 below Table 1 Voltage steps Steps 0 1 2 3 4 5 Wires Regulated output 230 VAC Voltages 0 80 110 140 170 190 230 Regulated output 115 VAC Voltages 0 40 55 70 85 95 115...

Page 10: ...evice is initialising Make sure the connections are correct before you power the unit Make sure the mains supply voltage is within the admissible rated maximum current of the product ATTENTION 1 Switch off the mains power supply before connecting any power cables 2 Install the connected sensor in an appropriate zone in order to measure the relevant ambient conditions 3 Select the operating mode vi...

Page 11: ... be ON above 51 and OFF below 49 An example of forward switching mode when Min Step 0 and Max Step 5 is given in Fig 4 below The thresholds are at 17 and hysteresis delta is set from 2 to 10 via Holding Register 16 see Fig 4 Fig 4 Automatic mode forward Low to high speed 68 85 110 0 140 170 190 230 17 34 51 Δ 25 50 75 100 1 0 Δ 140 170 190 230 Modbus RTU control signal Hysteresis 2 10 Uout VAC 3 2...

Page 12: ...r is lost the article stays on the last step selected If both communications are lost device stays on the last step selected In Auto modes if there is no communication to the control monitoring station the article continues to operate autonomously while the sensor is connected 18 Sensor output register value number Select which sensor output will be used as input to the device Digital potentiomete...

Page 13: ...fications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the ...