www.sentera.eu
MIW-RTVS8-EN-000 - 16 / 02 / 2022
5 - 13
RTVS8
115—230 VAC TRANSFORMER FAN SPEED
CONTROLLER WITH MODBUS RTU COMMUNICATION
■
EMC Directive 2014/30/EC:
►
EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
►
EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residential, commercial and light-industrial
environments
►
EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
■
WEEE Directive 2012/19/EC
■
RoHs Directive 2011/65/EC
WIRING AND CONNECTIONS
Wiring and connections
Terminal block
N
MOTOR
Regulated output to motor, neutral
L
Regulated output to motor, line
Pe
Protective earth terminal
N
RELA
Y
Unregulated output that can be set manually (ON/OFF) or
automatically via Modbus Holding register 19 and 15
L
N
INPUT
Power supply, neutral
L
Power supply, phase (230 VAC / 50—60 Hz)
TK
Input - TK monitoring for thermal motor protection
TK
2 - RJ45 master socket - to connect a Sentera sensor-transmitter for demand
based control, or a digital potentiometer for manual control
Pin 1
24 VDC
Supply voltage
Pin 2
Pin 3
A
Modbus RTU communication, signal A
Pin 4
Pin 5
/B
Modbus RTU communication, signal /B
Pin 6
Pin 7
GND
Ground, supply voltage
Pin 8
3 - RJ45 gateway - to connect a computer with 3SModbus software, Sentera
internet gateway or a BMS system
Pin 1
Do not connect to your computer
Pin 2
Pin 3
A
Modbus RTU communication, signal A
Pin 4
Pin 5
/B
Modbus RTU communication, signal /B
Pin 6
Pin 7
Do not connect to your computer
Pin 8
/B
A
GND
24 VDC
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
3
4
5
6
3
4