MT

ELECTRONIC FAN SPEED 
CONTROLLER

PRODUCT DESCRIPTION

The MT controllers provide manual control of the rotational speed of voltage 
controllable motors (230 VAC / 50 Hz) by varying the supplied voltage through 
phase angle control. They are suitable for both inset and surface mounting. Several 
motors can be connected as long as the current limit is not exceeded. All models 
have an extra (unregulated) 230 VAC output. 

ARTICLE CODES

Output regulation from minimum to maximum

Code

Current range, [A] 

Fuse, [A] (5*20  mm)

MTY-0-05-AT

 0,05—0,5

F-0,63 A-H 

MTY-0-15-AT

0,1—1,5

F-2,00 A-H 

MTY-0-25-AT

0,2—2,5

F-3,15 A-H

MTY-0-40-AT

0,4—4,0

F-5,00 A-H

Output regulation from maximum to minimum

Code

Current range, [A] 

Fuse, [A] (5*20  mm)

MTX-0-05-AT

 0,05—0,5

F-0,63 A-H 

MTX-0-15-AT

0,1—1,5

F-2,00 A-H 

MTX-0-25-AT

0,2—2,5

F-3,15 A-H

MTX-0-40-AT

0,4—4,0

F-5,00 A-H

INTENDED AREA OF USE

 

Manual control of the motor / fan speed in HVAC applications

 

For indoor use only

TECHNICAL DATA

 

Infinitely variable fan speed control

 

Power supply: 230 VAC ±10 % / 50 Hz

 

Unregulated input / output: 230 VAC / max. 2 A

 

OFF position can be disabled to obtain continuous operation of the fan

 

Regulated output: 80—230 VAC

 

Minimum speed adjustment by trimmer

 

Speed control:

 

MTX – from maximum to minimum

 

MTY – from minimum to maximum

 

Enclosure: 

 

External: ASA, white-ivory (RAL9010), IP54 (according to EN 60529)

 

Internal: polyamide, white-ivory (RAL9010), IP44 (according to EN 60529)

 

Operating ambient conditions:

 

temperature: 0—35 °C

 

rel. humidity: < 100 % rH (non-condensing)

 

Storage temperature: -10—40 °C

STANDARDS

 

Low Voltage Directive 2006/95/EC 

 

 EN 60335-1:2012 Household and similar electrical appliances - Safety - Part 1: 
General requirements. Amendment A11:2014 and AC:2014 to EN 603351;2012 

 

 EN 61558-1:2005 Safety of power transformers, power supplies, reactors and 
similar products - Part 1: General requirements and tests. Amendment A:2006 
and A1:2009 to EN 61558-1:2005

Summary of Contents for MT

Page 1: ...MT ELECTRONIC FAN SPEED CONTROLLER Mounting and operating instructions ...

Page 2: ...ER Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 ...

Page 3: ...uct performance Make sure the work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconn...

Page 4: ...H MTX 0 40 AT 0 4 4 0 F 5 00 A H INTENDED AREA OF USE Manual control of the motor fan speed in HVAC applications For indoor use only TECHNICAL DATA Infinitely variable fan speed control Power supply 230 VAC 10 50 Hz Unregulated input output 230 VAC max 2 A OFF position can be disabled to obtain continuous operation of the fan Regulated output 80 230 VAC Minimum speed adjustment by trimmer Speed co...

Page 5: ...supply voltage connected to and N OFF position disabled supply voltage connected to and N Uout Us Umin range 70 Min Max Off Switch On 0 20 Potentiometer position Uout Us Umin range 70 Min Max 0 20 Potentiometer position MTY series from minimum to maximum OFF position enabled supply voltage connected to and N OFF position disabled supply voltage connected to and N Uout Us Umin range 70 Min Max Off ...

Page 6: ...f the external enclosure 3 Dothewiringaccordingtothewiringdiagram seeFig 1 Wiringandconnections Fig 1 Wiring and connections Minimum speed adjustment trimmer Fuse holder with a spare fuse 4 Mount the internal enclosure into the wall according to the mounting dimensions shown in Fig 2 Mounting dimensions inset mounting Fig 2 Mounting dimensions inset mounting 82 82 26 33 50x50 62 50 62 60 62 50 62 ...

Page 7: ... Mount back the cover using the nut 10 Put back the knob and turn it to off position NOTE A 5 mm hole can be drilled at the bottom of the external enclosure to drain the condensed water OPERATING INSTRUCTIONS The controller is to be used only with voltage controllable fans motors You can connect several motors to the controller as long as the current limit is not exceeded The motor used should be ...

Page 8: ...to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnect...

Reviews: