Fig. 1 Mounting dimensions
Fig. 2 Mounting position
A
B
E
D
F
C
Article code
A
B
C
D
E
F
AH2A1-6
AH2A1-6
202 mm
115 mm
63 mm
102 mm
140 mm
Ø 4,60 mm
Correct
Incorrect
3.
Fix the unit onto the wall or panel using the provided screws and dowels. Mind
the correct mounting position and unit mounting dimensions (see
Fig. 1
Mounting
dimensions
and
Fig. 2
Mounting position
).
4.
Insert the low voltage cables through the cable glands and connect them to the
relevant terminals (refer to section
Operating Instructions
below for further
details).
5.
Put back the cover and secure it with the screws.
6.
Switch on the mains supply.
OPERATING INSTRUCTIONS
AH2A1 can operate as a Slave device only, i.e. an expansion unit. It can be controlled
via Modbus or, in case you do not intend to use Modbus, you can set it via the DIP
switches (see
Fig. 5
below). AH2A1 needs to be connected to an external master
controller in order to operate.
Follow these steps (see Fig. 3):
1.
Connect the mains supply to L, N and Pe.
2.
Connect the heater to the output terminal block - terminals N and H.
3.
Connect the unit to a master device (e.g. AH2C1-6) via inserting the low voltage
cables through one of the cable glands and connect them to GND and Ai1 of the
terminal block.
Fig. 3 Basic wiring and connections
230 VAC / 400 VAC
MASTER
Heater
AH2A1-6
ELECTRONIC HEATING
CONTROLLER