START-UP 

 

Page 7 

PRESSURIZING

 

 

1.

 

Put the bypass system in 'bypass' position. 

2.

 

Make  sure  the  electronic  controller  of  the  water 
softener is 'in service'.  

3.

 

Open the mains water supply. 

4.

 

Open  a  cold  treated  water  faucet  nearby  the  water 
softener and let the water run for a few minutes until 
all  foreign  material  that  may  have  resulted  from  the 
installation is washed out; close the tap. 

5.

 

Gently  pressurize  the  water  softener,  by  putting  it 
into service: 

 

factory bypass: 

1.

 

open the 'outlet' valve; 

2.

 

slowly open the 'inlet' valve.  

 

3-valve bypass: 

1.

 

close the 'bypass' valve; 

2.

 

open the 'outlet' valve; 

3.

 

slowly open the 'inlet' valve. 

6.

 

After  2-3  minutes,  open  a  cold  treated  water  faucet 
nearby the water softener and let the water run for a 
few  minutes  until  all  air  is  purged  from  the 
installation; close the tap. 

7.

 

Check  the  water  softener  and  all  hydraulic 
connections for leaks. 

 
 

BRINE CABINET 

 
8.

 

Add water conditioner salt to the brine cabinet. 

 
 

ELECTRONIC CONTROL PANEL 

 
9.

 

Program  the  electronic  controller  (refer  to  section 
'ELECTRONIC CONTROL PANEL'). 

 
 

INITIATE A REGENERATION 

 

10.

 

Manually  initiate  a  regeneration,  by  pressing  the 

scroll

 

 button repeatedly until the display shows:  

 
 
 

11.

 

Leave  the  water  softener  in  this  position;  the 
countdown timer will countdown to 0 sec and start a 
regeneration. 

 
 

 

 

Regen in 10 sec 

Summary of Contents for Eco

Page 1: ...OM ENG SentenciaEco Rev2010 10 O OW WN NE ER R S S M MA AN NU UA AL L Eco Eco WATER SOFTENER SYSTEM ...

Page 2: ...ll in the following data INSTALLATION RECORD Serial Number _______________________________________________ Model ________________________________________________________ Water Hardness inlet _______________________________________ Water Hardness outlet _____________________________________ Water Pressure inlet ________________________________________ Date of Installation __________________________...

Page 3: ... by a competent person aware of the local codes in force All plumbing and electrical connections must be done in accordance with local codes Before setting up the water softener make sure to check it for any externally visible damage do not install or use when damaged Use a hand truck to transport the water softener To prevent accident or injury do not hoist the water softener over your shoulder D...

Page 4: ...outdoor elements such as direct sunlight or atmospheric precipitation do not install the water softener too close to a water heater keep at least 3 m of piping between the outlet of the water softener and the inlet of the water heater water heaters can sometimes transmit heat back down the cold pipe into the control valve always install a check valve at the outlet of the water softener ELECTRICAL ...

Page 5: ...ater softener untreated water outlet of water softener treated water house application treated water 1 Screw the factory bypass onto the elbow connections of the water softener make sure to install the gasket seals Tighten the nuts firmly by hand 2 Screw the brass connection kit with nuts onto the factory bypass make sure to install the gasket seals Tighten the nuts firmly by hand 3 Connect the ma...

Page 6: ...o the drain solenoid of the control valve secure it by means of a clamp 2 Run the drain hose to the drainage system and connect it to the stand pipe assuring sufficient air gap This drain line operates under pressure so it may be installed higher than the water softener 3 Connect a 13 mm hose to the overflow elbow located at the back side of the water softener secure it by means of a clamp 4 Run t...

Page 7: ...he bypass valve 2 open the outlet valve 3 slowly open the inlet valve 6 After 2 3 minutes open a cold treated water faucet nearby the water softener and let the water run for a few minutes until all air is purged from the installation close the tap 7 Check the water softener and all hydraulic connections for leaks BRINE CABINET 8 Add water conditioner salt to the brine cabinet ELECTRONIC CONTROL P...

Page 8: ...ginning TIMER FAILURE In the event of a timer failure the display will show the message In such case entering one of the programming levels can possibly solve the problem However if the problem persists professional service is required SERVICE MODE In service mode the display shows the time of day and the remaining number of days REGENERATION MODE In regeneration mode the display shows the actual ...

Page 9: ... the display will show Press the up button or down button to set the language 2 Press the scroll button again the display will show Press the up button or down button to set the time of day 3 Press the scroll button again the display will show Press the up button or down button to set the hardness of the incoming untreated water Language English Set time 20 51 Set hardn XX f ...

Page 10: ...o the house application refill swimming pool irrigation WITH FACTORY BYPASS optional SERVICE POSITION inlet valve to water softener is OPEN outlet valve from water softener is OPEN BYPASS POSITION inlet valve to water softener is CLOSED outlet valve from water softener is CLOSED WITH 3 VALVE BYPASS SYSTEM not included SERVICE POSITION bypass valve is CLOSED inlet valve to water softener is OPEN ou...

Page 11: ...t to break it apart 3 pour warm water over the top of the salt to dissolve it BRINE CABINET To retain the appearance of the water softener simply wipe it with a damp cloth or clean it with a mild soap solution never use abrasive cleaners ammonia or solvents RESIN CLEANER Other contaminants f e iron present in the feed water can cause the resin bed to foul up resulting in a loss of softening capaci...

Page 12: ... draw brine Improper brine refill time setting Verify that brine refill time corresponds to the proper salt level and amount of resin Missing brine refill flow control Verify that flow control is installed and properly sized Leak from control valve to brine cabinet Clean or replace plunger and solenoid diaphragm of refill solenoid Salt taste in treated water Excessive water in brine tank Refer to ...

Page 13: ...or brine restrictor Clean injector and or brine restrictor Plugged injector filter Clean injector filter Restricted drain line Verify drain line for kinks or restrictions Restricted brine line Verify brine line for kinks or restrictions Leak in brine line Verify brine line and connections for air leakage No water in brine tank Refer to problem Control valve fails to refill brine tank Backwash sole...

Page 14: ...93 Salt usage per regeneration kg 3 1 4 1 9 2 5 3 3 4 0 Exchange capacity per kg salt m x f 41 Exchange capacity per kg salt m x d 23 Recommended maximum service flow m hr 1 1 1 5 2 0 2 6 3 2 Rinse water usage per regeneration 3 bars Ltr 3 59 80 92 116 141 2 Indicative numbers performances depending on operating conditions and water quality 3 Maximum salt water usage as brining is proportional min...

Page 15: ...32 44 58 75 Salt usage per regeneration kg 3 1 4 1 9 2 5 3 3 Exchange capacity per kg salt m x f 41 Exchange capacity per kg salt m x d 23 Recommended maximum service flow m hr 1 1 1 5 2 0 2 6 Rinse water usage per regeneration 3 bars Ltr 3 97 118 149 185 2 Indicative numbers performances depending on operating conditions and water quality 3 Maximum salt water usage as brining is proportional mini...

Page 16: ...NOTES Page 16 ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Reviews: