31
Setup Menu:
If the correct
password is entered, the unit will
display the Setup Menu Screen.
From the Setup Menu, the operator
can access the refrigerant monitoring
settings (Sample Setup), the gas
code assigned to each refrigerant
programmed in the monitor, system
configurations
settings
and
the
contact screen.
IR Setup:
Press the “1” key to enter
Sample Setup. The sample setup
screens allow the user to set the gas
code for the refrigerant to be
monitored, the distance of the tube
used for the sample, and the Low,
Main and high alarm thresholds.
The first sample setup screen will
display the gas code and the
distance. The cursor can be moved
by entering information, or if the
information is correct, pressing the
“ENT” key.
Press the left or right arrow keys to
change from one gas type to
another. The gasses are organized
in numerical order, with refrigerants
first, and fire suppression agents or
blowing agents following refrigerants.
Once
the
appropriate
gas
is
displayed, press the “ENT” key to
move the cursor from line two to line
three.
As of January 1, 2003 the standard
IR-SNIF monitor is capable of
detecting and responding to the
following list of refrigerants.
R-11, R-12, R-13, R-22, R-113, R-
114, R-123, R-134A, R-401A, R-
401B, R-402B-HP81, R-404A-HP62,
R-407A-AC9000, R-408A, R-409A,
R-410A-AZ20, R-500, R-502, R-503,
R-507-AZ50
Enter the tube length, in feet, if the
tube length is greater than 100 feet.
If the tube is shorter than 100 feet,
leave the setting at the factory
default of 100. When the distance
has been entered, press the “ENT”
key to display the second sample
setup screen.
Unless specified otherwise, SenTech
Corporation
recommends
the
following alarm settings for all
refrigerants
except R-123
:
Low = 25 ppm
Main = 50 ppm
High = 500 ppm
Unless specified otherwise, SenTech
Corporation
recommends
the
following alarm settings for R-123:
Low = 25 ppm
* SenTech Monitor *
ENTER PASSWORD
Followed By ENT
Code : 0
1)…IR Setup
2)…N/A
3)…System Setup
4)…Contact ABORT
Alarm Low 25 -
Alarm Main 50
Alarm High 500
ENT or ABORT
AREA 1
R-134A 8 <- ->
Distance 250
ENT or ABORT