User Manual 
LonWorks TP/FT-10 
Option module for PolluStat

 

 

M H 6144 INT, page 5 

4. Network 

variable 

list 

Designation 

Functional Block 

Network Variable 

Network Variable 

or Configuration 

Properties Type 

Data 

Value 

Range 

Unit 

Node Request 

NodeObject 

nviRequest 

SNVT_obj_request 

Node Status 

nvoStatus 

SNVT_obj_status 

FTP – File Transfer 
Request 

nviFileReq SNVT_file_req - - 

FTP – File Position 

nviFilePos 

SNVT_file_pos 

FTP – File Transfer 
Status 

nvoFileStat SNVT_file_status 

-  - 

Node Location 

SCPTlocation 

ASCII 

Heating Energy 

IntegralValues 

nvoHeatEnergy 

SNVT_reg_val_ts 

Int32 

kWh, MWh, 
MJ, GJ 

Heating Energy (Float) 

nvoHeatEnergyF SNVT_elec_whr_f IEEE754  Wh 

Cooling Energy 

nvoCoolEnergy 

SNVT_reg_val_ts 

Int32 

kWh, MWh, 
MJ, GJ 

Cooling Energy (Float) 

nvoCoolEnergyF SNVT_elec_whr_f 

IEEE754 

Wh 

Volume nvoVolume 

SNVT_reg_val_ts 

Int32 

(dm

3

), m

3

 

Volume (Float) 

nvoVolumeF SNVT_vol_f 

IEEE754 

(dm

3

Power InstantValues 

nvoPower 

SNVT_reg_val_ts 

Int32 

W, 

kW, 

MW 

Power (Float) 

nvoPowerF 

SNVT_power_f 

IEEE754 

Flow Rate 

nvoFlowRate 

SNVT_reg_val_ts 

Int32 

l/h 

Flow Rate (Float) 

nvoFlowRateF 

SNVT_flow_f 

IEEE754 

l/s 

Flow Rate (Fixed) 

nvoFlowRateP 

SNVT_flow_p 

Int16 

m

3

/h 

Forward temperature 

nvoForwardTemp 

SNVT_reg_val_ts 

Int32 

°C 

Forward temperature 
(Float) 

nvoForwardTempF SNVT_temp_f IEEE754 

°C 

Forward temperature 
(Fixed) 

nvoForwardTempP SNVT_temp_p 

Int16 

°C 

Return temperature 

nvoReturnTemp 

SNVT_reg_val_ts 

Int32 

°C 

Return temperature 
(Float) 

nvoReturnTempF SNVT_temp_f IEEE754 

°C 

Return temperature 
(Fixed) 

nvoReturnTempP SNVT_temp_p  Int16  °C 

Temperature difference 

nvoTempDiff 

SNVT_reg_val_ts 

Int32 

°C 

Temperature difference 
(Float) 

nvoTempDiffF SNVT_temp_f 

IEEE754 

°C 

Temperature difference 
(Fixed) 

nvoTempDiffP SNVT_temp_diff_p 

Int16 

°C 

Tariff Energy 1 

TariffEnergy[0] 

nvoTariffEnergy_1 

SNVT_reg_val_ts 

Int32 

kWh, MWh, 
MJ, GJ 

Tariff Energy 1 (Float) 

nvoTariffEnergyF_1 

SNVT_elec_whr_f 

IEEE754 

Wh 

Tariff Energy 2 

TariffEnergy [1] 

nvoTariffEnergy_2 

SNVT_reg_val_ts 

Int32

 

kWh, MWh, 
MJ, GJ

 

Tariff Energy 2 (Float) 

nvoTariffEnergyF_2 

SNVT_elec_whr_f 

IEEE754 

Wh 

Pulse Input Volume 1 

PulseInputVolume [0]  nvoPulseVolume_1 

SNVT_reg_val_ts 

Int32 

l (dm

3

), m

3

 

Pulse Input Volume 1 
(Float) 

nvoPulseVolumeF_1 SNVT_vol_f IEEE754 

(dm

3

Pulse Input Volume 2 

PulseInputVolume [1]  nvoPulseVolume_2 

SNVT_reg_val_ts 

Int32 

l (dm

3

), m

3

 

Pulse Input Volume 2 
(Float) 

nvoPulseVolumeF_2 SNVT_vol_f IEEE754 

(dm

3

  

 

Summary of Contents for LonWorks TP/FT-10

Page 1: ... between Network and Option Module 277 VRMS 0 60 Hz Number of LonWorks Devices per Segment Up to 64 Power down Network Protection High impedance when module is unpowered 1 3 Environmental requirements Operating Temperature ambient 5 to 50 C Storage Temperature 10 to 65 C Operating and Storage Humidity 25 to 90 RH 50 C non condensing 2 Safety instructions The installation electrical connection and ...

Page 2: ...onal pulse input or output 51 2nd additional pulse input or output In Out2 Volume output on TEST mode 52 GND for 1st additional pulse input or output 53 1st additional pulse input or output In Out1 Energy output on TEST mode LonWorks module clamp no Description 60 12 24 V AC DC SELV power supply 61 12 24 V AC DC SELV power supply 96 LonWorks TP FT 10 channel interface 97 LonWorks TP FT 10 channel ...

Page 3: ... 2700 3 Use only the dedicated terminators one terminator in free topology and two terminators on both ends of network channel in bus topology In case of any question please contact technical support 3 3 Integration in the LonWorks network It is recommended that the process of integration of the LonWorks option module setting the logical address and state of device as Configured and Online or defi...

Page 4: ... to reset the Update Rate parameter to default value 10 minutes 3 5 Firmware Update The option module firmware update can be done by user Downloading the firmware to device is performed by dedicated software run on Microsoft Windows operating system or by using the option Load application image and attach an Image file path to the Echelon OpenLNS Commissioning Tool during the module commissioning ...

Page 5: ...flow_f IEEE754 l s Flow Rate Fixed nvoFlowRateP SNVT_flow_p Int16 m3 h Forward temperature nvoForwardTemp SNVT_reg_val_ts Int32 C Forward temperature Float nvoForwardTempF SNVT_temp_f IEEE754 C Forward temperature Fixed nvoForwardTempP SNVT_temp_p Int16 C Return temperature nvoReturnTemp SNVT_reg_val_ts Int32 C Return temperature Float nvoReturnTempF SNVT_temp_f IEEE754 C Return temperature Fixed ...

Page 6: ...rror 0000 Hardware status flag Er02 bit2 Hardware status flag Er02 8000 Hardware status flag Er03 bit3 Hardware status flag Er03 8000 End of battery life time bit4 End of battery life time 1000 Hardware status flag Er05 bit5 Hardware status flag Er05 0008 Hardware status flag Er06 bit6 Hardware status flag Er06 0008 Flow sensor is empty Air in the ultrasonic flow sensor bit10 Flow sensor is empty ...

Page 7: ...nd left side Put the option module into the designated contact sockets The contact pins must not be bent Mount the fixing screws Install the additional battery into the second battery holder and plug in the connector to the second battery connector Route the connecting cable through an available cable fitting and make a pull relief Then connect the wires to the respective terminals Close the lid a...

Page 8: ...All trademarks are the property of their respective owners Edition 001 1503 030 0002 01A Subject to changes without notice Sensus GmbH Ludwigshafen Industriestraße 16 D 67063 Ludwigshafen Phone 49 0 621 6904 1000 Certified according to ISO 9001 Fax 49 0 621 6904 1409 Quality Management System Quality Austria Reg no 3496 0 E Mail info int xyleminc com www sensus com ...

Reviews: