Infrared Temperature Switch (Hot Metal Detector) Polaris PS09 / PI16
Communication via Serial Interface / Interface Commands
18
Command
Parameter
Description / Settings
bn
Read reference number (18-digit ASCII sequence)
Meaning: see
6.3
Type number
br
X
Baud rate (1-digit dec.)
X = 0-4, 6
0 = 1200 Baud
2 = 4800 Baud
4 = 19200 Baud
1 = 2400 Baud
3 = 9600 Baud
6 = 57600 Baud
em
XXXX
Emissivity (4-digit. dec.)
XXXX = 0020
–1000 in ‰ (= Emissivity 2–100%)
ez
X
Einstellzeit t
90
(1-stell. Dez.)
X = 0-6
0 = inherent time constant of the device
1 = 0.01 s
3 = 0.25 s
5 = 3 s
2 = 0.05 s
4 = 1 s
6 = 10 s
ga
XX
Device address (2-digit decimal number)
00
–97 = individual device address
99 = global address with answer
98 = global address without answer
gt
Read device temperature (2-digit decimal number in °C)
XX=00
–98°C
mb
Read temperature range (8-digit hexadecimal number)
First four digits: beginning of temperature range in °C
Last four digits: end of temperature range in °C
sw1
XXXXYYYY
Switch temperature 1 (8-digit hex.)
XXXX=lower switch temperature in °C
YYYY=upper switch temperature in °C
sw2
XXXXYYYY
Switch temperature 2 (8-digit hex.)
XXXX=lower switch temperature in °C
YYYY=upper switch temperature in °C
sn
Read serial number (5-digit decimal number)
tm
Read Maximum device temperature (2-digit decimal number),
XX=00
–98°C
ve
Read device type and software version (6-digit decimal number)
1. and 2. digit: Device type Polaris PS/PI
3. and 4. digit: Month of software version
5. and 6. digit: Year of software version