FA 46 Vision Sensor GB - 068-14297 - 10.02.2011-05
Mounting and
operating instructions
62
Sensor correctly connected?
- Power supply 24V DC
- Networkcable (not crossed) Nr. 902-51761
Electrical connection OK?
- green PWR LED at FA 46 active?
- Status LED at networkadapter active?
- and/or LAN Status shows "Connection
established". (system control
Network-
connections
LAN-Connection
Status)
Ask system administrator whether the IP
address 192.168.100.100/24 is free?
Connect Sensor correctly!
- Power supply 24V DC
- Networkcable (not crossed) Nr. 902-51761
no
yes
no
SensoFind finds Sensor with new IP?
- Start SensoFind
- Press button "Find"
- Mark Sensor
- Is "Connect" Button aktive?
Important:
To configure the FA 46 Vision Sensor for
the network,
it must be integrated in the network. Before connection, check whether
the sensor's address has already been assigned (default: 192.168.100.100/24). Network failure can otherwise occur.
Configuration of the sensor requires the FA 46 software and communication between sensor and PC. The sensor requires a
free IP address*1) to establish this connection.
"Repair" network connection
Check with system administrator,
can be problematic!
Start
system control
network connections
right mouse click on LAN connection
used
Repair (deletes ARP Cache).
Check IP connection
- in command prompt: ping xxx.xxx.xxx.xxx
(sensor's IP address*1) [ENTER] .
When four positive answers have been emitted, continue with
"yes" (Command prompt:
Start
All Programs
Accessories
Command prompt)
SensoFind starts applicaiton- software?
- Double click on sensor in list
- PC software starts
Check Sensor- and Softwareversion
Sensor version is displayed in SensoFind (e.g. 1.0.0.0). Compatibility
table and suitable software under www.sensopart.com
no
Parameter settings can now be carried out on
the sensor
Reconfigure alternative IP address via direction
connection (see 3.3.1.1. Direct connection)
no
yes
yes
yes
Configure sensor's IP address
Set IP
IP address *1) and enter subnet mask
set IP
restart sensor
(disconnect power supply for 6 sec.)
yes
yes
yes
yes
*1) a suitable, new, free IP address is assigned by the system administrator
SensoFind finds Sensor?
Insert sensor in network and switch on
start SensoFind
select sensor
yes
yes
no
Deacticate / adapt firewall
Check with system administrator
Check IP-Connection
When four positive answers are emitted, continue with "yes".
Attention!
Reactivate firewall once parameters settings have been
completed.
no
no
no
yes
yes
Proceeding/Troubleshooting - Network Connection
Establishing an operational Ethernet connection between FA 46 Vision Sensor and PC
Fig. 11
155-01199