Manual ver 2.0
23
Inp
Channel input probe 1
0
Value
Meaning
0
J : 0..600
°
C (Fe-CuNi, IEC584)
1
L : 0..600
°
C (Fe-CuNi, DIN43710)
2
K: 0..1200
°
C (NiCr-NiAl, IEC584)
3
N: 0..1200°C (NiCrSi-NiSi, IEC584)
4
T: 0..400°C (Cu-CuNi, IEC584)
5
R: 0..1600°C (Pt/13%Rh-Pt, IEC584)
6
S: 0..1600°C (Pt/10%Rh-Pt, IEC584)
7
RTD, Pt100: -200..600
°
C (IEC751)
8
RTD, Pt100: -99,9..200,0
°
C (IEC751)
9
Voltage V DC 0..5 V (Impedance >1 Mohm)
10
Voltage V DC 0..10 V (Impedance >1 Mohm)
11
Current loop 0..20 mA (load 150 ohm)
12
Current loop 4..20 mA (load 150 ohm)
13
Pressure transducer( only AK30 )
14
Extensiometric gauge 350 ohm ( only AK30 )
Unit
Unit 0
Value
Meaning
0 ºC
1 F
Dp
Position of the decimal point
0
In.L
Lower value for scale of inputs of linear signals
0
In.H
Higher value for scale of inputs of linear signals
99999
FSV
Pressure scale base or extensiometric gauge
99999
Type
Pressure transducer type
0
Value
Meaning
0
-3 a 37 mV transducer. Auto-calibration 0-80%
1
0 a 100 mV transducer. Auto-calibration 0-80%
2
0 a 100 mV transducer. Auto-calibration 0
Filtr
Display value filter for pressure measurement
0
Zero.S
Gauge zero voltage value
-3.00
FSV.S
Gauge maximum voltage value
37.00
Opt
Optional
functions 0
Value
Meaning
0 No
option
1 Communications
module
2
Analogue output 0..5 V
3
Analogue output 0..10 V
4
Analogue output 0..20 mA
5
Analogue output 4..20 mA
Set.Ch
Channel associated with analogue output
1
AOut.S
Analogue
output
sign
0
Value
Meaning
0 Direct
output