P a g e
40 | 82
Sensidyne Document No. 360-0257-01 (Rev A)
4.4.1.
From the System screen, select the Channel for ToD to be configured.
4.4.2.
Arrow to TOD Mode and the following submenus will appear:
Auto Mode
Test Day / Time
Days Between Tests
Cell Intensity
Output Indicators
4.4.3. Auto Mode
Enable is a convenient way to automatically perform a Test-On-Demand at
regular intervals (e.g., every 7 days).
NOTE: When Test-On-Demand is performed automatically and the test fails because gas is
present, system message will appear on the Normal Operation Mode Display and fault
output (if enabled) will appear.
4.4.3.1.
From the TOD Mode menu, Arrow to the Auto Mode submenu and select ENTER.
4.4.3.2.
Use the UP / DOWN arrows to Enable / Disable Test-On-Demand Auto Mode, and
select ENTER.
4.4.4. Test Day / Time
selects the date and time of for Test-On-Demand to be initiated while in
Auto Mode.
4.4.4.1.
From the TOD Mode menu, Arrow to the Test Day / Time submenu and select
ENTER.
4.4.4.2.
Select the date and time to initiate Test-On-Demand. The frequency of future Test-
On-Demand schedules will be established in additional steps.
4.4.5. Days Between Tests
establishes the frequency of Test-On-Demand bump tests starting
from the Test Day / Time selection.
4.4.5.1.
From the TOD Mode menu, Arrow to the Days Between Tests submenu and select
ENTER.