7.0 Using an AGS
61
© 2020 Sensata Technologies
7.0 Using an AGS
The ME-RC remote’s AGS menus under the AGS and TECH buttons allow
you to customize and monitor the operating parameters of the ME-AGS-N
(Automatic Generator Start - Network) controller. To help con
fi
gure and
operate the AGS with your ME-RC, refer to the mini index below to direct
you to the appropriate section.
7.1 AGS Setup
page 61
7.2 AGS Functional Tests
page 65
7.3 AGS Operation/Monitoring
page 65
7.4 Enabling the AGS
page 68
7.5 Starting and Stopping the Generator
page 68
7.6
AGS
Menu
Map page
69
Inverting
DC 12.6V 5A
SHORE
AGS METER SETUP TECH
AGS and TECH Buttons
Figure 7-1, ME-RC’s AGS Confi guration Access Buttons
7.1 AGS
Setup
Press the AGS button on ME-RC remote (Figure 7-1), and then rotate
the SELECT knob to navigate to the AGS menus. These menus allow the
generator to be automatically started and stopped based on different
parameters. Using Table 7-1, determine the speci
fi
c autostart and autostop
condition with which you want the generator to be automatically controlled,
and then use that speci
fi
c menu setting to con
fi
gure the AGS.
Note:
For information on using the AGS: 01 AGS Control, AGS: 02 AGS
Status, and AGS: 08 AGS TECH menus, refer to Section 7.3 “AGS Operation/
Monitoring”.
Table 7-1, ME-RC Autostart/Autostop Matrix
Autostart
Condition
See AGS Menu
Autostop
Condition
See AGS Menu
Gen starts on high
temperature, or
04 Start Temp F
(page 62)
Gen stops after a
set time period, or
03 Run Time Hour
(page 62)
Gen starts on low
inverter battery
voltage
05 Start Volts
(page 63)
Gen stops at Quiet
Time
07 Quiet Time
(page 64)