3.0 Setup
Button
FEATURES/SETTINGS
Inverter
Level
Required
Default
Setting
Main
Heading
Menu
Item
Selections/
Adjustments Range
SETUP (Cont.)
07 Power
Save
PwrSave= OFF, 1 - 60 Minutes
≥
Level 1
15min
08 Screen
Setup
Contrast=
0 - 100%
≥
Level 1
100%
**
Brightness=
50%
**
09 Final
Charge
Final=
Multi, Float, Silent
≥
Level 4
Multi
Silent
Rebulk =
(12.0-16.0V)
*
12.0V
10 Pwr Up
Always
Pwr Up= YES, NO
≥
Level 1
NO
11 Bulk
Always
Bulk Always= ON, OFF
≥
Level 1
OFF
TECH
01 Tem-
peratures
BTS:
Read only displays
≥
Level 1
Read
Only
Tfmr:
FETs:
AGS:
02 Revi-
sions
Inverter:
Read only displays
≥
Level 1
Read
Only
Remote:
AGS:
BMK:
Router:
03 Inv-
Model
Model: Read only display
≥
Level 1
Read
Only
04 Load
Defaults
Defaults in x.xs Press SELECT (x5 secs)
for default settings
≥
Level 1
Read
Only
05 Ext
Control
VAC Dropout:
Read only display
(“INT” or “EXT”)
≥
Level 1
Read
Only
Charge Rate:
Shore Max:
06 Set
PIN
SETUP= Locked, Unlocked,
Change PIN (PIN= 0000)
≥
Level 1
Unlocked
*
12-volt values shown; they are different for 24v and 48v inverters.
**
These settings return to factory default when power to remote is removed.
ME-RC Compatibility Matrix Notes:
[1] Not available on MM/MM-E/MM-AE/MMS/MMS-E/MMSA/MMA models.
[2] AC Couple mode can be activated using Battery Type: Custom, only with
MS-PAE Series
≥
Rev 4.1 or MS/MS-PE Series
≥
5.0.
[3] The AC amps displays are not shown unless connected to MS-PAE, MS-PE
or MSH Series models.
[4] Level 2 and 3 inverters can be used, but Level 2 inverters are limited
from 1.0 hour to 4.5 hours, Level 3 inverters <Rev 4.1 are limited from 1.0
to 6.5 hours; and Level 3 inverters
≥
Rev. 4.1 (and MMS Rev 1.5) are limited
from 1.5 to 6.5 hours; any setting outside these limited ranges are not
recognized and reverts to the inverter’s default absorption time (2.0 hours).
[5] BM/SOC features require the ME-BMK (Battery Monitor Kit) to be installed.