Page 1: ...Form 122189 2012 Sensata Technologies 1 DC to AC POWER INVERTERS Quasi Sine Wave 3 Phase Output MODEL 24TX60 OWNER S INSTRUCTIONS...

Page 2: ...INVERTER MODEL 24TX60 Table of Contents Page 1 Safety Instructions 3 2 Specifications 4 3 Technical Description 5 6 4 Inverter Description 7 5 Status Panel Description 8 6 Installation 9 11 7 Operatio...

Page 3: ...ray The Inverter System should not be installed in a zero clearance enclosure Damage to the Inverter System will occur if correct polarity is not observed when installing the DC input cables Damage to...

Page 4: ...ency Better than 85 Other Design Features Vent less for moisture and dust resistance Will withstand vibrating environment Thermally controlled cooling fan Elapsed time hour meter Remote panel with LED...

Page 5: ...nd and directed into the transformer which steps the voltage up to 120 volts The signal output waveform shape is not sinusoidal it has a total harmonic distortion of 35 and a maximum single harmonic d...

Page 6: ...ave Heyco strain relief connectors that are to be tightened as follows Sealing nut outside of the DC box is to be at 80 in lbs and the locking nut inside the box is to be set at 60 in lbs The AC cable...

Page 7: ...Inverter Physical Descriptions 4 1 Inverter Module FIGURE 2 Chassis physical description and installations dimensions FIGURE 3 DC Box See torquing requirements for cover plate round seal goes on outs...

Page 8: ...a Inverter power Green LED that indicates the inverter is operating from in Inverter Mode b Low battery Red LED that indicates the inverter is in a Low Battery voltage condition c Overload Red LED tha...

Page 9: ...inch diameter screws to secure the inverter See figure 5 6 2 1 The following instructions should be thoroughly read and understood before installation 6 2 2 CAUTION Inverters produce hazardous voltage...

Page 10: ...erter UL requires that the fuse be within 18 inches of the battery Cable gauge Line fuse 24TX60 4 0 500 amp 6 4 3 Use only an approved fuse holder with a U L listed fuse as indicated above 6 4 4Using...

Page 11: ...This model designation has a remote On Off switch circuit modified to accept 12 VDC The remote switch must be connected to the violet wire marked Remote Switch Hookup 6 6 220Y 120 VAC Output 6 6 1 CA...

Page 12: ...sure the DC wires are clean and tight Check the DC voltage at the inverter DC input Check or bypass the remote On Off circuit Low battery Red LED indicator Indicates that the inverter has shut off du...

Page 13: ...nsata warrants to the original purchaser for use that the goods or any component thereof manufactured by Dimensions will be free from defects in workmanship from the date of purchase for the period li...

Page 14: ...Form 122189 2012 Sensata Technologies 14 NOTES...