background image

Form: 122189 © 2012 Sensata Technologies 

12

 

 

7 Operation and Troubleshooting 

 

7.1

 

Operation 

To operate the inverter, switch the output circuit breaker switch to “ON”. Also switch 

“ON” the remote on/off switch (if used).

 

 
 
 

7.1.2

 

Turning  the  inverter  “ON”:

  To  turn  the  inverter  ON,  set  the  On/Off  switch  to  the  “On” 

position. The green “Inverter Power” LED will light.

 

 
 
 

7.2 

Troubleshooting  

 
Call  or  e-mail  Customer  Service  Department  for  free  consultation  during  business  hours  (central  time 
zone) at: 1-800-553-6418 or 1-651-653-7000; fax: 1-651-653-7600;  
E-mail: [email protected] 

 

 

A  TRUE  RMS  voltmeter  is  required  for  accurate  AC  output  voltage  measurements  on  a  quasi-sine 
inverter. A voltmeter that uses averaging circuitry will give incorrect measurements. 

 

Unplug  all loads  and  connect a 100-watt light bulb to the inverter  output. Observe  the LED Status 
Panel then check troubleshooting Table V. 

 

Table V 

PROBLEM 

POSSIBLE CAUSES OR SOLUTIONS 

No  LEDs:

  No  power  output.  The 

inverter  is  not  connected  to  the 

batteries;  the  battery  voltage  is 
below  9  volts  DC  or  there  is  a 
fault in the remote On/Off circuit. 

Check  the  in-line  fuses  for  continuity.  Make  sure  the  DC  wires  are 
clean  and  tight.  Check  the  DC  voltage  at  the  inverter  DC  input. 

Check or bypass the remote On/Off circuit. 
 

Low battery:

 Red LED indicator. 

Indicates  that  the  inverter  has 
shut  off  due  to  a  low  battery 

voltage condition. 

Fault in the battery wiring, battery capacity and voltage or the in-line 
fuse. The inverter will shut off after 2.5 seconds. Switch the inverter 
off then on to clear the error. 

Overload: 

Red  LED  indicator. 

Indicates  that  the  inverter  has 
shut  off  due  to  an  overload 
condition. 

The  inverter  output  wiring  is  shorting  or  loads  exceed  the  inverter 

rating.  The  inverter  will  shut  off  after  2.5  seconds.  Switch  the 
inverter off to clear the error. Remove the short circuit or excessive 
load from the output, and then switch the inverter on.  

High  Temp:

  Red  LED  indicator 

light.  Indicates  that  the  inverter 
has  shut  off  due  to  high  internal 

temperature. 

The 

unit 

will 

automatically  turn  back  on  when 

it has cooled to 40°C (104°F). 

Verify that the inverter is in a vented compartment and that the fan 
is  not  blocked.  High  ambient  temperatures  combined  with  poor 
ventilation may also contribute to the shut down. 

 

 

 
  
 

 
 

 
 

The battery voltage must be higher than 9 volts for the inverter to operate.

 

 
 

Turn  the  inverter  OFF  when  not  in  use.  There  is  an  approximated  1  to  2  amp  DC 
draw from the batteries at idle or no load. 

Summary of Contents for 24TX60

Page 1: ...Form 122189 2012 Sensata Technologies 1 DC to AC POWER INVERTERS Quasi Sine Wave 3 Phase Output MODEL 24TX60 OWNER S INSTRUCTIONS...

Page 2: ...INVERTER MODEL 24TX60 Table of Contents Page 1 Safety Instructions 3 2 Specifications 4 3 Technical Description 5 6 4 Inverter Description 7 5 Status Panel Description 8 6 Installation 9 11 7 Operatio...

Page 3: ...ray The Inverter System should not be installed in a zero clearance enclosure Damage to the Inverter System will occur if correct polarity is not observed when installing the DC input cables Damage to...

Page 4: ...ency Better than 85 Other Design Features Vent less for moisture and dust resistance Will withstand vibrating environment Thermally controlled cooling fan Elapsed time hour meter Remote panel with LED...

Page 5: ...nd and directed into the transformer which steps the voltage up to 120 volts The signal output waveform shape is not sinusoidal it has a total harmonic distortion of 35 and a maximum single harmonic d...

Page 6: ...ave Heyco strain relief connectors that are to be tightened as follows Sealing nut outside of the DC box is to be at 80 in lbs and the locking nut inside the box is to be set at 60 in lbs The AC cable...

Page 7: ...Inverter Physical Descriptions 4 1 Inverter Module FIGURE 2 Chassis physical description and installations dimensions FIGURE 3 DC Box See torquing requirements for cover plate round seal goes on outs...

Page 8: ...a Inverter power Green LED that indicates the inverter is operating from in Inverter Mode b Low battery Red LED that indicates the inverter is in a Low Battery voltage condition c Overload Red LED tha...

Page 9: ...inch diameter screws to secure the inverter See figure 5 6 2 1 The following instructions should be thoroughly read and understood before installation 6 2 2 CAUTION Inverters produce hazardous voltage...

Page 10: ...erter UL requires that the fuse be within 18 inches of the battery Cable gauge Line fuse 24TX60 4 0 500 amp 6 4 3 Use only an approved fuse holder with a U L listed fuse as indicated above 6 4 4Using...

Page 11: ...This model designation has a remote On Off switch circuit modified to accept 12 VDC The remote switch must be connected to the violet wire marked Remote Switch Hookup 6 6 220Y 120 VAC Output 6 6 1 CA...

Page 12: ...sure the DC wires are clean and tight Check the DC voltage at the inverter DC input Check or bypass the remote On Off circuit Low battery Red LED indicator Indicates that the inverter has shut off du...

Page 13: ...nsata warrants to the original purchaser for use that the goods or any component thereof manufactured by Dimensions will be free from defects in workmanship from the date of purchase for the period li...

Page 14: ...Form 122189 2012 Sensata Technologies 14 NOTES...

Page 15: ...the latest version of the relevant information to verify before placing any orders that the information being relied upon is current Sensata assumes no responsibility for infringement of patents or ri...

Reviews: