mA

4 5 6

+

mA

4 5 6

MI003422-E

ENGLISH - 3/4

OUTPUT

ACTIVE OUTPUT

: use this connection when the output loop is to be

powered directly from the Z109S-DI module.
The Z109S -DI module can supply a maximum load of 600 Ω, with loop
power supply protected against short circuit.

PASSIVE OUTPUT

: use this connection in case of external current

loop power supply

I

I

ELECTRICAL CONNECTIONS

For signal connections please use shielded cables; the equipment cable
shields must be connected to an instrumentation preferential ground.
It is also a good rule to avoid routing cables near power installation

cables, such as for transformers, inverters, motors, induction ovens, etc.

HOW TO INSTALL

Z109S-DI module is designed to be

on a

bar,

installed

IEC EN 60715

in a vertical position.
For correct operation and extended life, make sure that adequate
ventilation is provided for the module. Do not place raceways or other
objects in a way that might obstruct ventilation slots.
Do not install the module above equipment generating heat.
We recommend that the module is installed at the bottom of the cabinet.
We suggest you to install the module in the lower part of the cabinet.

HEAVY WORKING CONDITIONS:

Heavy working conditions are:

3

High power voltage ( > 30V

/ > 26 V    ).

~

~

3

Input sensor supply.
Use of output in impressed current.

For modules installed side by side, in the following cases

a separation

of at least 5 mm may be necessary

:

3

Upper board temperature higher than 45°C and at least one of the
heavy working conditions verified.

3

Upper board temperature higher than 35°C and at least two of the
heavy working temperature verified.

Summary of Contents for Z109S-DI

Page 1: ...0 mA loop impedance 600Ω Environemental conditions Temperature Humidity Storage temperature Protection degree From 20 to 60 C min 30 max 90 no condensing n From 30 to 85 C IP20 see the section How to install Box specification Dimensions and weight Material 100 x 112 x 18mm 130g PA6 Black colo r u Errors referred to Input s measure range Connections Removable 3 way screw terminals 5 mm pitch cable ...

Page 2: ...opriately sized fuse ELECTRICAL CONNECTIONS POWER ACTIVE INPUT use this for the two wire connection of transducers The transducer is directly powered by the Z109S DI module 20V 20mAmax protected against short circuit PASSIVE INPUT use this connection if the input current is external external loop power supply EN61000 6 4 electromagnetic compability industrial environment EN61000 6 2 electromagneti...

Page 3: ...o be on a bar installed IEC EN 60715 in a vertical position For correct operation and extended life make sure that adequate ventilation is provided for the module Do not place raceways or other objects in a way that might obstruct ventilation slots Do not install the module above equipment generating heat We recommend that the module is installed at the bottom of the cabinet We suggest you to inst...

Page 4: ...e negative consequences to the environmentandhumanhealth For more detailed information about the recycling of this product please contact your local city office wastedisposalserviceortheretailstorewhereyoupurchasedthisproduct SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 e mail info seneca it www seneca it Thisdocumentisproperty ofSENECAs r l Duplicat...

Reviews: