mA

7 8 9

+

mA

7 8 9

2 3

10-40V

C

19-28V

A

MI003422-E

ENGLISH - 2/4

Power voltage must be between 10 and 40 V

(indifferent polarity),

~

19 to 28 V

; see also

~

INSTALLATION NORMS.

Upper limits must not be exceeded, or the module could be
seriously damaged.

the power source must be protected from possible module failure by
means of an appropriately sized fuse.

ELECTRICAL CONNECTIONS

POWER

ACTIVE INPUT

: use this for the two-wire connection of transducers.

The transducer is directly powered by the Z109S-DI module 20V ,

~

20mA max., protected against short circuit.

PASSIVE INPUT

: use this connection if the input current is external

(external loop power supply).

EN61000-6-4

(electromagnetic compability, industrial

environment)

EN61000-6-2

(electromagnetic immunity, Industrial

environment)

EN61010-1

(security)

Standards:

The equipment complies with the following standards:

INPUT

I

I

Summary of Contents for Z109S-DI

Page 1: ...0 mA loop impedance 600Ω Environemental conditions Temperature Humidity Storage temperature Protection degree From 20 to 60 C min 30 max 90 no condensing n From 30 to 85 C IP20 see the section How to install Box specification Dimensions and weight Material 100 x 112 x 18mm 130g PA6 Black colo r u Errors referred to Input s measure range Connections Removable 3 way screw terminals 5 mm pitch cable ...

Page 2: ...opriately sized fuse ELECTRICAL CONNECTIONS POWER ACTIVE INPUT use this for the two wire connection of transducers The transducer is directly powered by the Z109S DI module 20V 20mAmax protected against short circuit PASSIVE INPUT use this connection if the input current is external external loop power supply EN61000 6 4 electromagnetic compability industrial environment EN61000 6 2 electromagneti...

Page 3: ...o be on a bar installed IEC EN 60715 in a vertical position For correct operation and extended life make sure that adequate ventilation is provided for the module Do not place raceways or other objects in a way that might obstruct ventilation slots Do not install the module above equipment generating heat We recommend that the module is installed at the bottom of the cabinet We suggest you to inst...

Page 4: ...e negative consequences to the environmentandhumanhealth For more detailed information about the recycling of this product please contact your local city office wastedisposalserviceortheretailstorewhereyoupurchasedthisproduct SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 e mail info seneca it www seneca it Thisdocumentisproperty ofSENECAs r l Duplicat...