USER MANUAL – Z-SG
15
6) Power on the module
7) Keep pushed the calibration button (or in alternative, only for Z-SG model, use digital input)
until LED ERR is “ON”
8) Release the calibration button
9) Control that the LED ERR is flashing
10) Put the tare on the load cell
11) Keep pushed the calibration button (or in alternative use digital input signal for Z-SG model)
until LED ERR switches from flashing to “OFF”
The module has acquired the tare value.
12) Keep pushed the calibration button (or in alternative use digital input signal) until LED ERR
is “ON”
13) Release the calibration button
14) Control that the LED ERR is flashing
15) Put the known weight on the tare
16) Keep pushed the calibration button (or in alternative use digital input signal) until LED ERR
switches from flashing to “OFF”
The module has acquired the known weight value.
17) Power off the module
18) Switch the Dip-Switches SW2-
4 to “OFF” and SW2-5 to “ON”. In this way, the module is
calibrated.
19) Power ON the module
If the module is power off during this procedure, calibration setting is lost. Restart the
calibration procedure from the first point.