background image

ENGLISH 7/8

MI002875-E

After a time interval of about 1 minute, the timeout message on the slave devices actually 
belonging to the network disappears, returning to the normal functioning.The behavior just 
described can be observed if there is the absence of the Z-LINK1 device connected to the 
interested Modbus slave device, too (for example, the previous Z-LINK1 connected to the Z-
4AI via local bus).

Infact 

the Z-LINK1 devices can detect network paths with timing usually much higher 

than the timeout of the Modbus Master. 

Therefore, the PC (Modbus master) continuing to 

poll, but the network is still employed to locate the device no longer connected. In particular, 
the  requests  that  arrive  to  the  network  when  it  is  employed  by  another  request  will  be 
discarded, causing the subsequent failure on the slaves in the list (timeout temporary).

Use of the network

To use the devices in the best way, mind the following points: 
1. All RS485 buses headed by a Z-LINK1 must be properly polarized and terminated.
2. The packet sending for Modbus broadcast (Modbus address 0x00) is supported by the 
network;  anyway,  for  multihop  MESH  topologies,  it  is  strongly  discouraged  because  it 
involves long communication times and low reliability of achieving all network elements.
3.  For  networks  constituted  by  a  large  number  of  devices,  avoid  the  densification  of 
infrastructural elements within the same covering range. 

Important points:

- Only for the Z-LINK1 configured in REMOTE I/O modality as master, the max number of 
input/output that can be configured in the I/O repetition map:
* is 20, for digital inputs/outputs
* is 50, for analog inputs/outputs
- The Easy setup software allows to negate the status of digital outputs, compared with the 
corresponding  input;  allows  to  scale  the  analog  inputs,  repeating  the  values  ​​in  the 
corresponding analog outputs. In both cases, it is possible to set the fail conditions.
- It is advisable to connect the (digital or analog) outputs in the Modbus master local bus 
- At the first start, the master module checks which slaves belong to the network effectively. 
For this reason: first, power on the Z-LINK1 «slave» devices; final, power on the   Z-LINK1 
«master» module
- In the Easy Setup software (in Test configuration window) there is a incremental counter, to 
display  eventual  fails  in  the  modules  connected  and  the  radio  communication  quality.  In 
correspondence of each module of displayed I/O map, there is a flag that signals eventual I/O 
fails in reading/writing.

PC

(master)

Z-LINK1

(SW1-1

=on)

bus RS485

Z-4AI

Z-LINK1

(SW1-1

=off)

bus RS485

Z-8TC

Z-LINK1

(SW1-1

=off)

bus RS485

timeout

timeout

(temporary)

Summary of Contents for Z-LINK1

Page 1: ...he Z LINK1 can be used SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manual and configuration softwares see www seneca it This document is property o...

Page 2: ...S protocol Z LINK1 represents a new platform communication in radio frequency Interface ModBUS RTU protocol Delay between polls Timeout master Modbus Frequency band Modulation Class of radio module Pe...

Page 3: ...nna IDC10 connector for Seneca bus Humidity 20 85 without condensing Mounting For DIN 46277 rail Dimensions weight 100 x 112 x 17 5 mm 200 g Case PBT black Accessories Cable RJ10 DB9F PM001420 Directi...

Page 4: ...e sides of the rear IDC10 connector to fix the module In case of Z PC DINAL 2 17 5 accessory the signals may be provided by terminal blocks The figure shows the meaning of the terminals and the positi...

Page 5: ...itch 1 ON state Default configuration Dip switch settings The module Z LINK1 has the RS232 communication port by RJ10 or screw terminals 4 5 6 1 as shown in the following figure The RJ10 port is the R...

Page 6: ...STER THAT QUERIES MODBUS SLAVES ARE THE SAME OF INTERNAL RADIO MODULE To complete the configuration set if the Z LINK1 is the Modbus master To complete the configuration of Z LINK1 follow the procedur...

Page 7: ...imes and low reliability of achieving all network elements 3 For networks constituted by a large number of devices avoid the densification of infrastructural elements within the same covering range Im...

Page 8: ...itable for safety applications 1 2 3 4 5 6 S L1 L2 Z LINK1 7 8 9 RJ10 COM ANTENNA L4 X L3 Disposal of Electrical Electronic Equipment Applicable throughout the European Union and other European countr...

Reviews: