background image

TECHNICAL SPECIFICATIONS

STANDARDS

EN61000-6-4

 

Electromagnetic emissions, industrial environment.

EN61000-6-2

 

Electromagnetic immunity, industrial environment.

 

N61010-1 

Safety.

INSULATION

Using an insulated conductor, its sheath determines the insulation voltage.

An insulation of 3 kV ac is guaranteed on bare conductors

ENVIRONMENTAL 

CONDITIONS

T

emperature

-25 – + 70 °C

 

Humidity

10%– 90% non condensing.

Altitude: 

Up to 2000 m above sea level 

Storage temperature:

 

-40 – + 85°C

 

Degree of protection: 

IP20.

ASSEMBLY

35mm DIN rail IEC EN60715, wall mounted with dowels, suspended with ties

CONNECTIONS

Removable 6-way screw terminals, 5 mm pitch for cable up to 2.5 mm

2

micro USB (CONFIGURATION ONLY)

POWER SUPPLY

Voltage: on Vcc and GND terminals, 11.5 – 28 Vdc;

Absorption: Typical: 21 mA (LOAD EXCLUDED)

COMMUNICATION 

PORT

RS485 serial port on terminals A+ and B-

INPUT

Type of measurement

:  AC/DC TRMS or DC Bipolar

Crest factor

2

Pass-band: 

1 kHz

Overload: 

2000 A impulsive, 3 x I

N

 continuing

CAPACITY

AC/DC True RMS (DIP7=OFF)

DC Bipolar (DIP7=ON)

T201DCH600-MU

0 – 300A or 0 - 600A

-300 – +300A or -600 - +600A

ANALOGUE 

OUTPUT 

on Vout and 

GND terminals

Type

0 – 10 Vdc, minimum load R

LOAD

 =2 kΩ.

Protection

Reverse polarity protection and over voltage protection

Resolution: 

13 bit (10000 points)

EMI error: 

< 0.5%

Temperature coefficient

< 200 ppm/°C

Hysteresis on measurement

:  0.2% of full scale

Response speed: 

With «Fast» filter 800 ms. With «Slow» filter 2000 ms.

The type of output can be selected via software

DIGITAL 

OUTPUT 

on DO and GND 

terminals

Type

: active, 0 – Vcc, maximum load 50 mA

The type of output can be selected via software

ACCURACY

below 2% of full scale

above 2% of full scale

T201DCH600-MU

1% of full scale at 50/60 Hz, 23°C

0.5% of full scale at 50/60 Hz, 23°C

OVERVOLTAGE 

CATEGORIES

Bare conductor: 

CAT. III 300 V

Insulated conductor: 

CAT. III 600 V

3/4

ATTENTION

Please, install the module as shown in the figure.  Pay attention to the direction 
of the current flow.
To increase the current measurement sensitivity, insert the cable several times 
into the central hole of the instrument, creating a series of coils. The current 
measurement sensitivity is proportional to the number of turns