4/4
SETTING THE DIP-SWITCHES
The position of the DIP-switches defines the Modbus communication parameters of the module: Address and
Baud Rate. The following table shows the values of the Baud Rate and the Address according to the setting of the
DIP-switches:
DIP-Switch status
POSITION
ADDRESS
POSITION
BAUD
RATE
POSITION
TYPE OF
MEASUREMENT
POSITION
MEASURING
SCALES
1 2 3 4
5 6
7
8
#1
9600
AC/DC true RMS
Full scale
#2
19200
DC Bipolar
Half scale
#3
38400
DIP-switches must be set while the module is not
powered on in order to avoid damaging it.
KEY
#...
57600
#14
The instrument is supplied configured for 600 A (DCH600), with 800 ms filter
inserted and TRMS mode selected.
ON
#15
OFF
All dip-switches set to OFF: parameters from flash memory. See the USER manual
Note:
When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).
ELECTRICAL CONNECTIONS
CONTACT INFORMATION
Technical support
Product information
U
sci
ta
(V)
Ingresso (A) TRMS
10
0
±600
±300
(DIP7 = OFF)
5
Ingresso (A) DC Bipolar
-600
0+ +300
-300
(V)
(DIP 7 = ON)
+600
Uscita
Output (V)
Input (A) TRMS
Input (A) DC Bipolar
Output (V)
USB PORT
CU MICROO TG
-A
CU
MICROB
-A-
CU
MICROB
-A-
Configurazione
tramite APP
Android
Configurazione
tramite
software PC
The module is designed to exchange data according to the modes defined by the MODBUS protocol. It has a micro
USB connector on the front panel and can be configured using applications and/or software programs.
The USB serial port uses the following communication parameters:
38400,8,N,1
The USB communication port responds exactly like the serial ports, with the exception of the communication
parameters. For more information, visit the site shown on page 1.
Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.
-
-
Android APP
configuration
PC software
configuration
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.
The content of this document corresponds to the described products and technologies.
Stated data may be modified or supplemented for technical and/or sales purposes.
Vcc
GND
A+
B-
DO
Vout
+
V