The T121 instrument converts input signals and retransmits them into a normalized current signal for 4 - 20 mA 
loop.  The  input  signals  may  come  from  J,  K,  R,  S,  T,  B,  E,  N  thermocouples  (EN  60584),  RTD  sensors 
(thermistors) as Pt100 (EN 60751), Ni100 (DIN 43760), Pt500, Pt1000 and moreover, the instrument T121 can 
acquire voltage and resistance values. TheRTD input may be with 2,3 or 4 wire connection.

GENERAL DESCRIPTION

ENGLISH - 2/8

MI001963-E

t

OUTPUT / POWER SUPPLY

voltage

Operating 
Current output
Load resistance

Resolution
Output in case of over-range
Output in case of fault
Current output protection

 
7 – 30 V

C

Loop 4 – 20 mA

C

1 kΩ @ 26 V , 21 mA

C

(see: Load Resistance / Minimum operanting voltage Diagram)

μ

A (> 13 bit)

102.5% of full-scale (see Over-range table)
Programmable between 3.4 and 23 mA (see Fault table)
< 30mA

POTENTIOMETER INPUT

Potentiometer value
Energizing current
Input impedance
Sensor fault detection

 
Potentiometer resistance: up to 1700 Ω without exernal resistor.
375 

μ

A

10 M

Ω

Yes, may be disabled

THERMOCOUPLE INPUT

Input impedance
Cold junction compensation
Sensor fault detection

 
10 M

Ω

- 40 

 +85 

±

 1.5 

°

C

Yes, may be disabled

TECHNICAL SPECIFICATIONS

l

High accuracy.

l

16 bit conversion measurement.

l

Insulation 1500 V

A

.

l

Compact size and fast connections with spring terminals.

l

All parameters can be configured with dedicated software: EASY SETUP downloadable from the website 
www.seneca.it in the T121 software section.

GENERAL CHARACTERISTICS

MODULE LAYOUT

44 mm

17 mm

18.5 mm

4 mm

4 mm

6 mm

25 mm

8 mm

3.75 mm

M4 x 25

Weight

35 g.

Case

Material PA6 reinforced with glass-fibre, black color.

Summary of Contents for T121

Page 1: ...d technologies described in it This informations may be modified or integrated for technical and or commercial requirements SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fa...

Page 2: ...m 2 A 13 bit 102 5 of full scale see Over range table Programmable between 3 4 and 23 mA see Fault table 30mA POTENTIOMETER INPUT Potentiometer value Energizing current Input impedance Sensor fault de...

Page 3: ...aused by EMI 300 ms 620 ms 60 dB at 50 and 60 Hz 0 5 EMI ElectroMagnetic Interference STANDARDS EN61000 6 4 Electromagnetic emission industrial environment EN61000 6 2 Electromagnetic immunity industr...

Page 4: ...ple J K T N E 0 05 0 05 0 5 C Thermocouple B R S 0 05 0 05 1 C RTD 0 05 0 05 0 1 C Resistor 0 05 0 05 40 m Resistor 0 05 0 05 200 m Voltage 0 05 0 05 15 V Potentiometer 0 05 0 05 0 01 EMI ElectroMagne...

Page 5: ...tweenmoduleandprobe youshouldrememberthatthisconnection introduces an error in the measurement which can be removed by software programming equivalent to the resistance contributedbytheconnectioncable...

Page 6: ...ction 2wires 3wiresand4wires Measurementfilter disabledorenabled Output Normal 4 20mA orreversed 20 4mA Inputtype Cableresistancecompensationfor2wiresmeasurement Outputcurrentvalueincaseoffailure Valu...

Page 7: ...n case of fault Over Range To terminals 3 and 4 YES enabled NO disabled NO disabled K 0 C 1000 C 21 mA YES limited output between 2 5 and 102 5 FACTORY SETTINGS 2 PROGRAMMING CONNECTOR ACCESS 2 CONNEC...

Page 8: ...ces CUSTOMIZATION OF THE INTERPOLATION CURVE The EASY SETUP software allows the configuration of the T121 module in order to linearise also the sensors included in the above table Custom if their oper...

Reviews: