Input measurement range table

Type

Input

Measurement

Range

Calibration

error

EMI

(*)

Minimum

Span

Resolution

Standard

Thermocouple

J

-210° 

 1200 °C

0.1 %

< 0.5 %

50 °C

5 μV

EN 60584

K

-200° 

 1372 °C

0.1 %

< 0.5 %

50 °C

5 μV

EN 60584

R

-50° 

 1768 °C

0.1 %

< 0.5 %

100 °C

5 μV

EN 60584

S

-50° 

 1768 °C

0.1 %

< 0.5 %

100 °C

5 μV

EN 60584

T

-200° 

 400 °C

0.1 %

< 0.5 %

50 °C

5 μV

EN 60584

B(**)

0° 

 1820 °C

0.1 %

< 0.5 %

100 °C

5 μV

EN 60584

E

-200° 

 1000 °C

0.1 %

< 0.5 %

50 °C

5 μV

EN 60584

N

-200° 

 1300 °C

0.1 %

< 0.5 %

50 °C

5 μV

EN 60584

RTD

Ni100

-60° 

 250 °C

0.1 %

< 0.5 %

20 °C

DIN 43760

Pt100

-200° 

 650 °C

0.1 %

< 0.5 %

20 °C

EN 60751

Pt500

-200° 

 650 °C

0.1 %

< 0.5 %

20 °C

28 

Pt1000

-200° 

 200 °C

0.1 %

< 0.5 %

20 °C

28 

Voltage

mV

-150 

 150 mV

0.1 %

< 0.5 %

2.5 mV

5 μV

Potentiometer

Ω

500  

 100 k

 Ω

Ω

0.1 %

< 0.5 %

10 %

0.0015 %

Resistor

Ω

 400 

Ω

0.1 %

< 0.5 %

10 

Resistor

Ω

 1760 

Ω

0.1 %

< 0.5 %

50 

28 

Accuracy measurement table: the greater between the value of the sum A + B and the value C

Input type

A: % of measurement

B: % of Span

C: Minimum

Thermocouple J, K, T, N, E

0.05 %

0.05 %

0.5 °C

Thermocouple B, R, S

0.05 %

0.05 %

1 °C

RTD (***)

0.05 %

0.05 %

0.1 °C

Resistor

0.05 %

0.05 %

40 

Resistor

0.05 %

0.05 %

200 

Voltage

0.05 %

0.05 %

15 μV

Potentiometer

0.05 %

0.05 %

0.01 %

(*) 

EMI: 

ElectroMagnetic Interferences.

(**) 

TC B:  ThermoCouple B: between 0° and 250 °C the measurement is null.

(***) 

RTD:  ThermoResistor: Errors calculated on the resistive value of sensor.

PRELIMINARY WARNINGS

Before performing any operation it is mandatory to read the full contents of this manual.

The module may only be used by qualified and skilled technicians in the field of electric installation.

 www.seneca.it/products/t121.

Specific documentation is available for download at website:

Only  the  Manufacturer  is  authorized  to  repair  the  module  or  to  replace  damaged  parts. 
The  product  is  susceptible  to  electrostatic  discharge,  take  appropriate  countermeasures
during any operation.

The warranty is null and void in case of improper use or tampering of the module or devices 
supplied by the Manufacturer, necessary for its correct operation, if the instructions in this 
manual have not been complied with.

ENGLISH - 4/8

MI001963-E

t

Summary of Contents for T121

Page 1: ...d technologies described in it This informations may be modified or integrated for technical and or commercial requirements SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fa...

Page 2: ...m 2 A 13 bit 102 5 of full scale see Over range table Programmable between 3 4 and 23 mA see Fault table 30mA POTENTIOMETER INPUT Potentiometer value Energizing current Input impedance Sensor fault de...

Page 3: ...aused by EMI 300 ms 620 ms 60 dB at 50 and 60 Hz 0 5 EMI ElectroMagnetic Interference STANDARDS EN61000 6 4 Electromagnetic emission industrial environment EN61000 6 2 Electromagnetic immunity industr...

Page 4: ...ple J K T N E 0 05 0 05 0 5 C Thermocouple B R S 0 05 0 05 1 C RTD 0 05 0 05 0 1 C Resistor 0 05 0 05 40 m Resistor 0 05 0 05 200 m Voltage 0 05 0 05 15 V Potentiometer 0 05 0 05 0 01 EMI ElectroMagne...

Page 5: ...tweenmoduleandprobe youshouldrememberthatthisconnection introduces an error in the measurement which can be removed by software programming equivalent to the resistance contributedbytheconnectioncable...

Page 6: ...ction 2wires 3wiresand4wires Measurementfilter disabledorenabled Output Normal 4 20mA orreversed 20 4mA Inputtype Cableresistancecompensationfor2wiresmeasurement Outputcurrentvalueincaseoffailure Valu...

Page 7: ...n case of fault Over Range To terminals 3 and 4 YES enabled NO disabled NO disabled K 0 C 1000 C 21 mA YES limited output between 2 5 and 102 5 FACTORY SETTINGS 2 PROGRAMMING CONNECTOR ACCESS 2 CONNEC...

Page 8: ...ces CUSTOMIZATION OF THE INTERPOLATION CURVE The EASY SETUP software allows the configuration of the T121 module in order to linearise also the sensors included in the above table Custom if their oper...